Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberBLD01-02967
StatusExpired
Name SLETTEN COMPANIES
Site Address 11770 W PRESIDENT DR
Project NameW BOISE INDUSTRIAL PARK
Customer Number 
ePlanReviewNo
Description
(SLETTEN COMPANIES)(WEST BOISE INDUSTRIAL PARK) To remodel a 2,247 sq.ft. office per approved plans on file. Work to include creating 2 new offices and constructing 1 new accessible restroom. NOTE: This building was constructed in Ada County and annexed into Boise. Work to include, construction of interior partitions, installation of suspended ceiling system, construction of one-hour fire-resistive tenant demising walls, related interior finishes, separate permits required for Electrical, mechanical and plumbing work. This building is fully fire sprinklered for area increase, any alterations or modifications to the fire sprinkler system shall be per NFPA #13 as regulated by the fire department. (#pc855-01)*RmH*
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/23/20031/27/20031/24/2003ACANC
DetailsRuss Owen
john- ###-####--pending fire-fn occ Inspection cancelled from web by: Rita DeYoung
FIRE-Final Inspection1/23/20031/24/20031/24/2003AFAIL
DetailsTroy Cobbley
Phone #: ###-#### Provide signage on the fire riser door and provide Knox Box 1/24/2003 9:55:45 AM
BLD-Framing/Rough-in1/28/20021/28/20021/28/2002PPART
DetailsRuss Owen
celling grid john ###-####needs addnl perimeter wires 1/29/2002 1:31:57 PM
FIRE-Sprinkler Rough-in1/23/20021/24/20021/24/2002AFAIL
DetailsTroy Cobbley
Provide smoke detector, manual pull station and horn/strobe on the fire alarm system as well as 60 hour backupwith dual phone lines. Submitt plans to City of Boise. If panel is replaced HVAC units may need to be monitored. Provide exit sign at required exit, provide approved door hardware, provide tagged fire extinguishers mounted with handles at 48", provide heat in riser room (remove heat tape) and provide current inspection tag on riser. 1/24/2002 7:24:21 PM
BLD-Framing/Rough-in1/8/20021/9/20021/9/2002APART
DetailsRuss Owen
STE C ###-#### JOHN. ok to rock, after ele,plm approvals. 1/9/2002 1:06:15 PM
BLD-Framing/Rough-in1/3/20021/3/20021/3/2002PPART
DetailsRuss Owen
###-#### Conference on exiting. 1/3/2002 3:00:24 PM