BLD-Final | 4/16/2002 | 4/17/2002 | 4/17/2002 | A | PASS |
Tom Arcoraci
|
|
|
###-#### Chuck call for access ok for perm occ 4/17/2002 10:27:20 AM
|
BLD-Final | 4/12/2002 | 4/12/2002 | 4/12/2002 | P | PART |
Russ Owen
|
|
|
###-####ok temp oc, c/n for restroom 4/12/2002 4:27:20 PM
|
FIRE-Final Inspection | 4/12/2002 | 4/12/2002 | 4/12/2002 | A | PASS |
Troy Cobbley
|
|
|
Fire life/safety OK
|
FIRE-Final Inspection | 3/21/2002 | 3/22/2002 | 3/22/2002 | P | FAIL |
Troy Cobbley
|
|
|
all items on the correction notice are taken care of except for the addition of one duct detector. I notified builder that approved fire alarm plans will be required for this addition 3/22/2002 2:59:22 PM
|
BLD-Final | 3/19/2002 | 3/20/2002 | 3/20/2002 | P | NR |
Tom Arcoraci
|
|
|
###-#### CHUCK
|
FIRE-Final Inspection | 3/19/2002 | 3/20/2002 | 3/20/2002 | A | FAIL |
Troy Cobbley
|
|
|
provide 4" suite numbers, provide one fire extinguisher with current inspection tag mounted at 48" above finish floor, only one exit can have key locking hardware and that door must have sticker. The other door must have keyed hardware removed and approved door hardware provided, provide testing duct detector for tenant space, provide access to fire riser room so verification of monitoring and inspection tags 3/20/2002 10:38:22 AM
|
Permanent Occupancy | | 3/19/2002 | 3/19/2002 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 2/28/2002 | 3/1/2002 | 3/1/2002 | P | PASS |
Tom Arcoraci
|
|
|
CHUCK ###-####
|