Permit Information
Permit NumberBLD02-00137
StatusExpired
Name ADA COUNTY OPERATIONS
Site Address 7200 W BARRISTER DR
Project NameADA COUNTY PUBLIC SAFETY BLDG
Customer Number 
ePlanReviewNo
Description
(ADA COUNTY OPERATIONS) To remodel a 3,072 sq.ft. portion of basement area for use as dispatch office area and equipment room. Work to include, removal of existing non bearing partitions, construction of new partitions, installation of approximatley 377 sq ft of new suspended ceiling area, installation of a new door access system, Miscelaneous related interior finishs. NOTE: This building is fully fire sprinklered, any alterations or modifications to the fire sprinkler system shall be per NFPA #13 as regulated by the fire department. (#pc050-52)rmh
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection2/18/20042/18/20042/18/2004 CANC
DetailsTom Arcoraci
BLD-Aging Inspection12/19/200312/19/200312/19/2003 PASS
DetailsTom Arcoraci
BLD-Final9/8/20039/9/20039/9/2003PPASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 9/8/2003 at 11:06:02 AM. Contact: ###-####. SCOTT IS POC ok for perm 9/9/2003 4:11:56 PM
FIRE-Final Inspection8/28/20039/3/20039/3/2003APASS
DetailsTroy Cobbley
Fire life safety is ok. Owner to hang the two existing fire extinguishers this morning. One wall that was to be demo'd is to remain 9/3/2003 10:28:47 AM
BLD-Aging Inspection7/30/20037/30/20037/30/2003 NR
DetailsTom Arcoraci
needs fire insp 7/30/2003 1:10:04 PM
BLD-Final8/7/20028/8/20028/8/2002ANR
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 08/07/2002 at 16:22:10. Contact: ###-####.
FIRE-Final Inspection8/7/20028/8/20028/8/2002AFAIL
DetailsTroy Cobbley
provide tamper switches on the valves for the fire pump and the fire sprinkler riser.These switches are to be monitored by the fire alarm system. The bypass valve for the fire pump is in the open position. Provide information as to why and close the valve. Provide supervision of the new duct smoke detector by the fire alarm panel. Provide approved fire alarm drawings for items 1 and 4 on the correction notice. Sprinkler heads in the phone room and the radio room are overspaced. Verify beam blockage in radio room 8/8/2002 11:24:16 AM
BLD-Framing/Rough-in4/24/20024/25/20024/25/2002APART
DetailsDave Hannah
fr insp jeff- pager ###-#### or cell ###-#### or site # ###-#### none load bearing wall with no elec between com and opperations room ok to cover 4/25/2002 9:59:23 AM
BLD-Conference4/2/20024/9/20024/9/2002APASS
DetailsTom Arcoraci
###-#### ok to 1 side drywall before struc insp 4/9/2002 10:30:27 AM