BLD-Final | 5/11/2004 | 5/11/2004 | 5/11/2004 | A | PASS |
Dave Hannah
|
|
|
|
Permanent Occupancy | | 5/11/2004 | 5/11/2004 | | DONE |
|
|
|
|
BLD-Final | 2/24/2004 | 2/25/2004 | 2/25/2004 | A | PART |
Dave Hannah
|
|
|
RANDY; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok for temp occ 2/25/2004 12:36:44 PM
|
FIRE-Final Inspection | 2/24/2004 | 2/25/2004 | 2/25/2004 | A | PASS |
Rick Jackson
|
|
|
RANDY; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
BLD-Final | 2/23/2004 | 2/24/2004 | 2/24/2004 | A | CANC |
Dave Hannah
|
|
|
Dennis; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
BLD-Final | 2/20/2004 | 2/23/2004 | 2/23/2004 | A | FAIL |
Dave Hannah
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
Code Occupancy Approval | | | 2/23/2004 | | PASS |
|
|
|
|
BLD-Final | 2/19/2004 | 2/20/2004 | 2/20/2004 | A | FAIL |
Troy James
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Annette Moore
Checked doors for closure, seal and hardware floors 2 through 6. 2/20/2004 11:11:12 AM
|
BLD-Final | 2/18/2004 | 2/18/2004 | 2/18/2004 | P | NR |
Dave Hannah
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD-Final | 2/17/2004 | 2/18/2004 | 2/18/2004 | A | NR |
Dave Hannah
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
FIRE-Final Inspection | 2/17/2004 | 2/18/2004 | 2/18/2004 | A | FAIL |
Rick Jackson
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Annette Moore need signs on FACP and sprinkler room doors; signs in stairwells; extinguishers in lobby and fire pump room; lobby doors can't locked to trap people in lobby area; need extinguishers in penthouse rooms and on all floors; need smoke seals on all rated doors and they must latch; need to verify emergency lighting in corridors; stairwells and exit systems must be free of construction materials; update keys in knox box; complete elevator recall/shunt and sign-off 2/18/2004 3:42:54 PM 2/18/2004 3:45:06 PM
|
BLD-Final | 2/9/2004 | 2/9/2004 | 2/9/2004 | P | NR |
Dave Hannah
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD-Framing/Rough-in | 2/4/2004 | 2/4/2004 | 2/4/2004 | P | PART |
Dave Hannah
|
|
|
dennis ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
BLD-Framing/Rough-in | 1/30/2004 | 1/30/2004 | 1/30/2004 | P | DONE |
Dave Hannah
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
BLD-Energy code compliance | 12/31/2003 | 12/31/2003 | 12/31/2003 | P | CANC |
Tom Arcoraci
|
|
|
Odie ###-####
|
BLD-Aging Inspection | 8/19/2003 | 8/19/2003 | 8/19/2003 | | PART |
Jim Storey
|
|
|
340 hase insp. for today. 8/19/2003 8:22:14 AM
|
BLD-Framing/Rough-in | 6/19/2003 | 6/19/2003 | 6/19/2003 | P | PART |
Carl Dependahl
|
|
|
4hr wall wip...ok 6/19/2003 5:25:27 PM
|
BLD-Framing/Rough-in | 5/5/2003 | 5/9/2003 | 5/9/2003 | A | PART |
Carl Dependahl
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore...add fireproof ing at col's, beams as spec'd...1hr at major members. 5/9/2003 4:54:43 PM
|
BLD-Conference | 5/8/2003 | 5/8/2003 | 5/8/2003 | P | CANC |
Carl Dependahl
|
|
|
|
BLD-Framing/Rough-in | 5/5/2003 | 5/8/2003 | 5/8/2003 | A | CANC |
Carl Dependahl
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Framing/Rough-in | 5/5/2003 | 5/7/2003 | 5/7/2003 | A | CANC |
Carl Dependahl
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Framing/Rough-in | 5/7/2003 | 5/7/2003 | 5/7/2003 | P | PART |
Carl Dependahl
|
|
|
4hr wall, wip ok. to 3rd level 5/7/2003 4:05:39 PM .. 5/7/2003 4:05:44 PM
|
BLD-Framing/Rough-in | 5/5/2003 | 5/6/2003 | 5/6/2003 | A | PART |
Carl Dependahl
|
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 4hr wall, wip, changed design above 3rd fl to 2layer ultra code gyp (3/4"), typical all firewalls; eng'r took no exceptions to eng'd framing for same submitted by ISI. 5/6/2003 1:19:09 PM
|
BLD-Conference | 4/18/2003 | 4/21/2003 | 4/21/2003 | A | PASS |
Carl Dependahl
|
|
|
rec'd resub for framing & GA assy of 4hr wall, need arch's ok? 4/21/2003 11:00:38 AM
|
BLD-Conference | 4/14/2003 | 4/14/2003 | 4/14/2003 | P | PASS |
Carl Dependahl
|
|
|
4hr walls , need clarify stud/brace details ... 4/14/2003 4:01:03 PM 4/14/2003 4:01:21 PM
|