BLD-Final | 11/6/2003 | 11/7/2003 | 11/7/2003 | P | PASS |
Tom Arcoraci
|
|
|
cecil--pending fire fn ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok for perm 11/7/2003 1:52:35 PM
|
FIRE-Final Inspection | 11/6/2003 | 11/7/2003 | 11/7/2003 | P | PASS |
Troy Cobbley
|
|
|
fire alarm, fire sprinklers and fire alarm finaled 11/7/2003 1:09:51 PM
|
Permanent Occupancy | | 11/7/2003 | 11/7/2003 | | DONE |
|
|
|
|
FIRE-Final Inspection | 10/27/2003 | 10/28/2003 | 10/28/2003 | A | FAIL |
Troy Cobbley
|
|
|
cecil ; Phone #: ###-#### Provide verification that the emergency lights and exit signs are on the emergency generator circuit 10/28/2003 2:50:11 PM
|
BLD-Other | 9/8/2003 | 9/8/2003 | 9/8/2003 | P | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 9/8/2003 at 8:51:50 AM. Contact: ###-####. wip ok 9/8/2003 2:02:52 PM
|
FIRE-Sprinkler Rough-in | 9/4/2003 | 9/5/2003 | 9/5/2003 | P | PASS |
Troy Cobbley
|
|
|
cecil; Phone #: ###-#### Remaining areas are ok to cover 9/5/2003 2:57:46 PM
|
BLD-Conference | 8/25/2003 | 8/25/2003 | 8/25/2003 | P | PASS |
Tom Arcoraci
|
|
|
grid ok in rooms 8/25/2003 3:22:55 PM
|
FIRE-Sprinkler Rough-in | 8/22/2003 | 8/25/2003 | 8/25/2003 | A | PART |
Troy Cobbley
|
|
|
See the approved plans for the rooms that the sprinkler pipig is OK to cover. Also see plans for location of sprinkler pendant that needs replaced, closet with missing pendant and the Soiled Linen room should be ordinary hazard spacing not light hazard 8/25/2003 10:59:17 AM
|
BLD-Wall cover | 8/12/2003 | 8/13/2003 | 8/13/2003 | A | PASS |
Tom Arcoraci
|
|
|
partial grid ok 8/13/2003 9:42:33 AM
|
FIRE-Sprinkler Rough-in | 8/12/2003 | 8/13/2003 | 8/13/2003 | A | PART |
Troy Cobbley
|
|
|
Inspection was for a cover inspection of 9 patient rooms on the south side of the 5th floor remodel. The rooms are ok to cover. See approved plans for exact locations 8/13/2003 9:36:50 AM
|
BLD-Framing/Rough-in | 5/7/2003 | 5/8/2003 | 5/8/2003 | P | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 5/7/2003 at 11:46:35 AM. Contact: ###-####. wip ok 5/8/2003 3:17:33 PM
|
BLD-Aging Inspection | 12/20/2002 | 12/20/2002 | 12/20/2002 | | PASS |
Tom Arcoraci
|
|
|
wip 12/23/2002 9:02:51 AM
|