BLD-Conference | 12/30/2002 | 12/30/2002 | 12/30/2002 | A | PASS |
Jim Storey
|
|
|
180 day extention work to start soon.
|
FIRE-Final Inspection | 9/12/2002 | 9/16/2002 | 9/16/2002 | A | FAIL |
Rick Jackson
|
|
|
###-#### sprinklers overspaced on southwest area of first floor; breakroom heads too close to each other on first floor; verify annual sprinkler inspection; escutcheons 9/16/2002 10:07:52 AM
|
BLD-Final | 9/12/2002 | 9/12/2002 | 9/12/2002 | P | FAIL |
Jim Storey
|
|
|
###-#### ###-#### need single function egress hardware and fire sprinkler walk through/ not sign off as insp by plan review but apears to be over spacing in some areas. 9/12/2002 1:26:50 PM
|