BLD-Final | 5/7/2003 | 5/8/2003 | 5/8/2003 | A | PASS |
Tony Young
|
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Darla Downs
ok for perm. occ. 5/8/2003 10:01:05 AM
|
Permanent Occupancy | | 5/8/2003 | 5/8/2003 | | DONE |
|
|
|
|
FIRE-Final Inspection | 4/30/2003 | 4/30/2003 | 4/30/2003 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm system finaled. OK for perm occupancy
|
BLD-Conference | 4/22/2003 | 4/23/2003 | 4/23/2003 | A | PART |
Tony Young
|
|
|
430 is checking 4/23/2003 9:38:41 AM
|
BLD-Conference | 4/22/2003 | 4/23/2003 | 4/23/2003 | A | DONE |
Troy Cobbley
|
|
|
I spoke with Charlie at simplexgrinnell and he said that they would get the inspection called in as soon as possible 4/25/2003 10:46:40 AM
|
BLD-Aging Inspection | 4/22/2003 | 4/22/2003 | 4/22/2003 | | PASS |
Tony Young
|
|
|
temp. occ. now,, waiting for trades 4/23/2003 9:39:34 AM
|
BLD-Final | 11/22/2002 | 11/22/2002 | 11/22/2002 | P | PART |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 11/22/2002 at 10:08:05. Contact: ###-####...need certify 45 min glazing at corr, verify htg NA? 11/22/02 5:53:14 PM
|
FIRE-Final Inspection | 11/22/2002 | 11/22/2002 | 11/22/2002 | P | PART |
Troy Cobbley
|
|
|
a temp. occupancy was given with dave millers permission until the fire alarm drawings have been approved, devices installed and tested 11/22/2002 3:47:04 PM
|
BLD-Final | 11/7/2002 | 11/8/2002 | 11/8/2002 | P | CANC |
Tony Young
|
|
|
Scheduled by a contractor via Hello! on 11/07/2002 at 09:19:08. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 11/08/2002 at 08:13:56.
|
FIRE-Final Inspection | 11/7/2002 | 11/7/2002 | 11/7/2002 | P | FAIL |
Troy Cobbley
|
|
|
provide one 2-A10BC fire extinguisher with current inspection tag mounted with handle at 48" in a normal path of travel. See note #3, repair exit signs in path of eress from tenant space to building exterior then test exit signs. Provide City of Boise approved fire alarm plans. See note #2. Replace the insulation above the sprinkler uprights along the north half of the new demising wall. Provide ceiling tile at the sprinkler pendants and replace the missing canopies. Remove the dry wall splatter from the sprinkler pendants. Provide a suite address for tenant and provide a key for the "knox box" 11/7/2002 1:53:58 PM
|
BLD-Framing/Rough-in | 10/15/2002 | 10/16/2002 | 10/16/2002 | A | PASS |
Tony Young
|
|
|
Scheduled by a contractor via Hello! on 10/15/2002 at 14:17:38. Contact: ###-####.
|
BLD-Framing/Rough-in | 10/9/2002 | 10/9/2002 | 10/9/2002 | P | FAIL |
Tony Young
|
|
|
Scheduled by a contractor via Hello! on 10/09/2002 at 09:16:36. Contact: ###-####.c/n posted on demising wall 10/9/2002 3:06:36 PM
|