BLD-Final | 11/22/2002 | 11/25/2002 | 11/25/2002 | A | PASS |
Jim Storey
|
|
|
l/c ok per approved plan. 11/25/2002 9:11:50 AM
|
BLD-Final | 11/21/2002 | 11/22/2002 | 11/22/2002 | P | FAIL |
Jim Storey
|
|
|
###-#### doug ###-#### doug need ada grab bar woman restaroom 11/22/2002 5:59:22 PM
|
FIRE-Final Inspection | 11/21/2002 | 11/22/2002 | 11/22/2002 | A | PASS |
Rick Jackson
|
|
|
###-#### doug
|
FIRE-Final Inspection | 11/18/2002 | 11/20/2002 | 11/20/2002 | A | FAIL |
Rick Jackson
|
|
|
###-#### DOUG adjust exit signs as shown on plans; main exit has manual flush bolts; landings at doors; need to test detectors on air handlers per UMC 608; building has fire alarm system and audiovisual not meeting NFPA 72 - need to submit plans (building doesn't require alarm system and isn't sprinklered) 11/20/2002 10:04:02 AM
|
BLD-Conference | 11/15/2002 | 11/18/2002 | 11/18/2002 | A | PASS |
Jim Storey
|
|
|
###-#### doug
|
BLD-Framing/Rough-in | 11/4/2002 | 11/4/2002 | 11/4/2002 | P | PASS |
Jim Storey
|
|
|
butch; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|