BLD-Final | 6/12/2003 | 6/12/2003 | 6/12/2003 | P | PASS |
Jim Sly
|
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Annette Moore OK for Perm Occ. :) :) 6/12/2003 1:31:13 PM
|
Permanent Occupancy | | 6/12/2003 | 6/12/2003 | | DONE |
|
|
|
|
BLD-Final | 6/9/2003 | 6/10/2003 | 6/10/2003 | A | FAIL |
Jim Sly
|
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Called Eric and told him that he needs fire final insp. 6/10/2003 12:18:39 PM
|
FIRE-Final Inspection | 6/10/2003 | 6/10/2003 | 6/10/2003 | P | PASS |
Troy Cobbley
|
|
|
fire life 6/10/2003 3:33:34 PM safety finaled 6/10/2003 3:33:48 PM
|
FIRE-Final Inspection | 5/13/2003 | 5/13/2003 | 5/13/2003 | A | FAIL |
Troy Cobbley
|
|
|
Repair the exit sign and the emergency light on the existing tenant side and provide approved door hardware on the restroom and tanning room doors
|
BLD-Final | 2/6/2003 | 2/10/2003 | 2/10/2003 | A | FAIL |
Jim Sly
|
|
|
###-#### eric Verbal.....Need all Req. signatures.......Electr in computer. 2/10/2003 10:02:34 AM
|
FIRE-Final Inspection | 2/10/2003 | 2/10/2003 | 2/10/2003 | P | FAIL |
Troy Cobbley
|
|
|
JERRY- CELL ###-####- Areas in new tenant area lack fire sprinkler coverage. Provide approved fire sprinkler plans before performing work. Provide approved door hardware on interior doors per review note #12. Provide approved door hardware on front exit in vew space aor blank off the existing hardware and remove existing exit sign per Ron Hill ###-####. Provide approved door hardware on both rear exit doors. See review notes #6 and #12. Repair exit signs and test the emergency light. Provide fire extinguishers and tag the existing fire extinguishers. 2/10/2003 1:37:41 PM
|
BLD-Framing/Rough-in | 11/25/2002 | 11/27/2002 | 11/27/2002 | A | PASS |
Jim Sly
|
|
|
J R ; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|