BLD-Final | 3/10/2003 | 3/10/2003 | 3/10/2003 | P | PASS |
Tom Arcoraci
|
|
|
RICHARD; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok for perm occ 3/10/2003 2:44:51 PM
|
Permanent Occupancy | | 3/10/2003 | 3/10/2003 | | DONE |
|
|
|
|
BLD-Final | 2/6/2003 | 2/7/2003 | 2/7/2003 | A | PART |
Russ Owen
|
|
|
or burell ###-####; Phone #: ###-#### Internet Inspection Request from: Rita DeYoungOk for a temp oc , need panic hdware front door as marked on plans, signage at right rear restroom, complete flooring at new openings. 2/7/2003 1:18:15 PM
|
FIRE-Final Inspection | 2/6/2003 | 2/6/2003 | 2/6/2003 | P | PASS |
Troy Cobbley
|
|
|
life safety finaled 2/6/2003 4:14:52 PM
|
FIRE-Final Inspection | 2/5/2003 | 2/5/2003 | 2/5/2003 | P | FAIL |
Troy Cobbley
|
|
|
BURRELL; Phone #: ###-#### Provide panic hardware on the new area main exit/entry doors per the approved plans. Remove the manual flush bolts from the rear exit doors unless approved by the building dept. Install the remaining door hardware 2/5/2003 2:28:13 PM
|
BLD-Framing/Rough-in | 1/14/2003 | 1/14/2003 | 1/14/2003 | P | PASS |
Tom Arcoraci
|
|
|
for bathrooms ###-#### burell ok for cover all 1/14/2003 1:24:19 PM 1/14/2003 1:24:38 PM
|
BLD-Framing/Rough-in | 1/10/2003 | 1/10/2003 | 1/10/2003 | P | FAIL |
Tom Arcoraci
|
|
|
burell; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie needs new ceiling josits at bath rooms needs headers at new openings ok to cover all but these areas 1/10/2003 3:35:28 PM
|