BLD-Aging Inspection | 6/2/2006 | 6/2/2006 | 6/2/2006 | | DONE |
Mike Jordan
|
|
|
|
DOC - Permit Finaled | 6/2/2006 | 6/2/2006 | 6/2/2006 | P | PASS |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 3/30/2006 | 3/30/2006 | 3/30/2006 | | CANC |
Mike Jordan
|
|
|
|
DOC - Permit Finaled | 3/30/2006 | 3/30/2006 | 3/30/2006 | P | DONE |
Mike Jordan
|
|
|
|
BLD-Final | 7/28/2003 | 7/29/2003 | 7/29/2003 | A | PASS |
Russ Owen
|
|
|
###-#### mark Ok perm oc, job done. 7/29/2003 2:35:05 PM
|
FIRE-Final Inspection | 7/25/2003 | 7/25/2003 | 7/25/2003 | P | PASS |
Troy Cobbley
|
|
|
fire alarm, fire sprinkler and fire life safety finaled
|
BLD-Final | 4/8/2003 | 4/9/2003 | 4/9/2003 | P | NR |
Russ Owen
|
|
|
They have failed the fire /life safety inspection and I will can not perform structural inspection untill this has been resolved. 4/9/2003 1:05:31 PM
|
FIRE-Final Inspection | 4/8/2003 | 4/9/2003 | 4/9/2003 | A | FAIL |
Rick Jackson
|
|
|
call Mark at ###-#### 4/8/2003 1:36:25 PM sprinklers overspaced at new walls and in conference room - need sprinkler plans; need alarm plans as notification is needed in break room and conference room 4/9/2003 12:05:36 PM
|
BLD-Final | 4/7/2003 | 4/8/2003 | 4/8/2003 | A | CANC |
Russ Owen
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie. needs fire lifesafety prior. 4/8/2003 2:10:33 PM
|
BLD-Final | 3/20/2003 | 3/20/2003 | 3/20/2003 | P | CANC |
Russ Owen
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Annette Moore. 3/20/2003 2:06:45 PM
|
BLD-Framing/Rough-in | 2/20/2003 | 2/24/2003 | 2/24/2003 | A | PASS |
Russ Owen
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie. ok to cover. 2/24/2003 10:10:47 AM
|