Permanent Occupancy | | 4/17/2006 | 4/17/2006 | | DONE |
|
|
|
|
BLD-Final | 4/13/2006 | 4/13/2006 | 4/13/2006 | P | PASS |
Tom Arcoraci
|
|
|
odie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok for perm occ
|
FIRE-Final Inspection | 4/5/2006 | 4/13/2006 | 4/13/2006 | A | PASS |
Troy Cobbley
|
|
|
fire life safety finaled
|
FIRE-Final Inspection | 4/4/2006 | 4/5/2006 | 4/5/2006 | A | CANC |
Troy Cobbley
|
|
|
to be rescheduled
|
BLD-Aging Inspection | 3/17/2006 | 3/17/2006 | 3/17/2006 | | NR |
Tom Arcoraci
|
|
|
|
FIRE-Final Inspection | 1/4/2006 | 1/4/2006 | 1/4/2006 | P | CANC |
Troy Cobbley
|
|
|
Duplicate inspection
|
FIRE-Final Inspection | 1/4/2006 | 1/4/2006 | 1/4/2006 | P | FAIL |
Troy Cobbley
|
|
|
odie; Phone #: ###-#### Remove thumbturn locks from all doors including the main exit. Provide sticker and indicator at the main exit. Sprinkler heads are overspaced on the Radiant Research side of the building in the sleep study area, outside the sleep study area on the north side and one pendant in the open office is too close to a column. Provide additional emergency lights as marked on the plans and repair the two emergency lights on the Selah side. Provide emergency lighting in the main lobby.
|
FIRE-Final Inspection | 11/28/2005 | 11/29/2005 | 11/29/2005 | A | CANC |
Troy Cobbley
|
|
|
No time for inspection
|
BLD-Aging Inspection | 10/26/2005 | 10/26/2005 | 10/31/2005 | | NR |
Troy Cobbley
|
|
|
I spoke to the building owner Scott and notified him that I had left a notice that the affected areas as described in the open building permits and fire permits would be shutdown/closed for use if all permits were not finaled by 11/11/05. The notice was left with Diane at the front desk. I spoke to Scott over the phone. He was going to contact Odie with Steed and Jim Danes with DeBest.
|
BLD-Aging Inspection | 8/15/2005 | 8/15/2005 | 8/17/2005 | | DONE |
Troy Cobbley
|
|
|
I spoke to Odie with Steed Construction and he will contact Debest Fire about getting their permit finaled.
|
BLD-Aging Inspection | 6/7/2005 | 6/7/2005 | 6/7/2005 | | NR |
Tom Arcoraci
|
|
|
needs fire
|
BLD-Aging Inspection | 4/4/2005 | 4/4/2005 | 4/6/2005 | | DONE |
Forrest France
|
|
|
I called Brian with AIC solutions, ###-####, and left a message on his voice mail requesting status of the fire alarm installation
|
BLD-Conference | 9/28/2004 | 9/28/2004 | 9/28/2004 | P | NR |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 9/28/2004 at 11:29:54 AM. Contact: ###-####. needs all sigs 9/28/2004 3:54:29 PM
|
BLD-Aging Inspection | 8/2/2004 | 8/2/2004 | 8/2/2004 | | NR |
Tom Arcoraci
|
|
|
|
BLD-Aging Inspection | 8/2/2004 | 8/2/2004 | 8/2/2004 | | NR |
Tom Arcoraci
|
|
|
|
FIRE-Final Inspection | 5/24/2004 | 5/25/2004 | 5/25/2004 | A | FAIL |
Troy Cobbley
|
|
|
Resubmit building plans showing as-built wall layout for the entire facility. Include correct room descriptions and locations of all rated walls, doors and glass. Room not shown on the plans in work area 157 has six bunk beds. Per on of the office personell this is used for overnight studies of insomnia. Provide description of this use and all other uses to the plan reviewer. Door hardware is not of approved type on some of the doors in the remodeled area and exit signs are not operating correctly. Atleast one sprinkler head is overspaced in the comference room. Pendant head in corridor outside of office 103 is too close to the wall (2") and a pendant head in storage room 134/135 exceeds 130 sq.ft. max. spacing. A full inspection will be conducted when revised plans are approved. 5/25/2004 11:25:48 AM
|
BLD-Aging Inspection | 4/6/2004 | 4/6/2004 | 4/6/2004 | | NR |
Tom Arcoraci
|
|
|
|
BLD-Final | 2/4/2004 | 2/5/2004 | 2/5/2004 | A | CANC |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 2/4/2004 at 7:32:50 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Feb 5 2004 7:20AM.
|
FIRE-Final Inspection | 2/4/2004 | 2/4/2004 | 2/4/2004 | P | FAIL |
Troy Cobbley
|
|
|
fire alarm plans are not approved yet 2/4/2004 2:03:48 PM
|
BLD-Framing/Rough-in | 1/23/2004 | 1/23/2004 | 1/23/2004 | P | PART |
Tom Arcoraci
|
|
|
odi celing inspection; Phone #: ###-#### Internet Inspection Request from: Darla Downs grid ok 1/23/2004 2:10:10 PM
|
BLD-Framing/Rough-in | 1/5/2004 | 1/5/2004 | 1/5/2004 | P | PASS |
Russ Owen
|
|
|
Odie---permit and drawing at the front counter.; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
BLD-Aging Inspection | 12/12/2003 | 12/12/2003 | 12/12/2003 | | NR |
Tom Arcoraci
|
|
|
wip 12/12/2003 7:59:53 AM
|