BLD-Final | 8/17/2004 | 8/17/2004 | 8/17/2004 | P | PASS |
Jim Storey
|
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles final ok 8/17/2004 12:30:23 PM
|
Permanent Occupancy | | 8/17/2004 | 8/17/2004 | | DONE |
|
|
|
|
FIRE-Final Inspection | 8/12/2004 | 8/12/2004 | 8/12/2004 | P | PASS |
Rick Jackson
|
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Emergency lights are located by elevator and at west stair door; fire/life safety okay 8/12/2004 3:17:08 PM
|
FIRE-Final Inspection | 8/6/2004 | 8/9/2004 | 8/9/2004 | A | FAIL |
Rick Jackson
|
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Need emergency lighting per plan review notes 8/9/2004 3:38:26 PM
|
BLD-Framing/Rough-in | 7/16/2004 | 7/16/2004 | 7/16/2004 | P | PASS |
Jim Storey
|
|
|
c/n made ok
|
BLD-Framing/Rough-in | 7/14/2004 | 7/15/2004 | 7/15/2004 | A | FAIL |
Jim Storey
|
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 1621.2.7 Partitions. Partitions that are tied to the ceiling
and partitions greater than 6 feet (1829 mm) in height
shall be laterally braced to the building structure. Such
bracing shall be independent of any ceiling splay bracing.
Bracing shall be spaced to limit horizontal deflection at... 7/15/2004 11:19:09 AM
|
BLD-Framing/Rough-in | 7/7/2004 | 7/8/2004 | 7/8/2004 | A | NR |
Tony Young
|
|
|
Tom; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
conf erence only about difference in plans as to how the walls where constructed,,, Tom will get w/ framer and or architect to resolve issues and recall. 7/8/2004 12:04:30 PM
|