Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberBLD04-01093
StatusFinaled
Name JOHN P PRICE
Site Address 802 W BANNOCK ST
Project NameHOFF BUILDING-7TH FLR
Customer Number 
ePlanReviewNo
Description
(HIGHWAY 12 - HOFF BUILDING - 7TH FLR) This building is fire sprinklered for building area increase, because it is a high-rise, and to comply with 1994 UCBC provisions. To remodel a 1,488 square foot area on the 7th floor of the Hoff Building for a new office occupant. This tenant will occupy about half of the floor. Work is to include interior nonbearing walls, interior doors, and interior windows all per the approved drawings and the plan review report on file. A total coverage smoke detection fire alarm system will be installed throughout the 7th floor in lieu of exit separation. If smoke is detected anywhere on the 7th floor, the entire 7th floor shall be alarmed. A separate alarm permit is required. Within the modified areas, fire sprinkler heads shall be located or relocated to comply with NFPA 13-2002 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/25/20051/25/20051/25/2005PPASS
DetailsDave Hannah
Scheduled by a contractor via Hello! on 1/25/2005 at 9:24:49 AM. Contact: ###-####. ok for perm occ 1/25/2005 2:08:15 PM
Permanent Occupancy 1/25/20051/25/2005 DONE
Details
Permanent Occupancy 1/25/20051/25/2005 DONE
Details
FIRE-Final Inspection1/20/20051/20/20051/20/2005APASS
DetailsRick Jackson
BLD-Final1/18/20051/18/20051/18/2005PCANC
DetailsDave Hannah
BLD-Final1/10/20051/10/20051/10/2005ACANC
DetailsDave Hannah
ok for temp occ ok for perm after alarm is finaled
BLD-Conference1/6/20051/7/20051/7/2005APASS
DetailsDave Hannah
Scheduled by a contractor via Hello! on 1/6/2005 at 3:12:25 PM. Contact: ###-####.
FIRE-Conference1/6/20051/7/20051/7/2005APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 1/6/2005 at 3:11:00 PM. Contact: ###-####. Temp occupancy approved per Dave M. pending resubmittals for fire alarm address changes 1/7/2005 10:45:36 AM
BLD-Framing/Rough-in9/9/20049/9/20049/9/2004PPART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 9/9/2004 at 9:33:46 AM. Contact: ###-####. ok to cover wall that have no elec in them and ok to cover the rest after elec r/i 9/9/2004 3:38:29 PM
BLD-Framing/Rough-in9/7/20049/8/20049/8/2004AFAIL
DetailsDave Hannah
Scheduled by a contractor via Hello! on 9/7/2004 at 3:31:16 PM. Contact: ###-####.add wall bracing remove screws from top track to ceiling grid 9/8/2004 2:40:38 PM