BLD-Final | 10/5/2004 | 10/6/2004 | 10/6/2004 | A | NR |
Lane Manuel
|
|
|
vance; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
need fire insp. prior to bldg. dept sign off 10/6/2004 9:29:06 AM
|
BLD-Final | 10/6/2004 | 10/6/2004 | 10/6/2004 | P | PART |
Lane Manuel
|
|
|
per your request
c of o ok to issue pending fire insp. approval. 10/6/2004 12:40:25 PM
|
FIRE-Final Inspection | 10/5/2004 | 10/6/2004 | 10/6/2004 | A | PASS |
Troy Cobbley
|
|
|
Life safety finaled 10/6/2004 11:05:48 AM
|
Permanent Occupancy | | 10/6/2004 | 10/6/2004 | | DONE |
|
|
|
|
FIRE-Final Inspection | 9/29/2004 | 9/29/2004 | 9/29/2004 | P | FAIL |
Troy Cobbley
|
|
|
Fire sprinkler permit needs finaled. Provide approved door hardware to storage room and provide verification of duct detector testing or test detector 9/29/2004 4:05:43 PM
|
BLD-Final | 8/23/2004 | 8/23/2004 | 8/23/2004 | P | NR |
Lane Manuel
|
|
|
KAREN; Phone #: ###-#### Internet Inspection Request from: Annette Moore
fire insp. req'd new plan submittal for variation from appr. plans. 8/23/2004 3:40:39 PM
|
FIRE-Final Inspection | 8/23/2004 | 8/23/2004 | 8/23/2004 | P | FAIL |
Troy Cobbley
|
|
|
Sprinkler pendants in backroom are overspaced and spaced too close in one spot. Sprinkler work will require permits. Provide approved door hardware on all doors per review note #22. Must unlock in a single motion. Remove deadbolt on the rear door. Building floor plans do not match what is installed. Resubmit plans, 2 copies, to city of boise. Reviewer is Dan Stuart, ###-####. Remove plastic exit signs. Provide verification HVAC unit has duct smoke detector per fire review note #35 and test 8/23/2004 4:19:12 PM
|
BLD-Final | 8/13/2004 | 8/16/2004 | 8/16/2004 | A | FAIL |
Lane Manuel
|
|
|
Vance ; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
BLD-Final | 8/13/2004 | 8/16/2004 | 8/16/2004 | A | FAIL |
Lane Manuel
|
|
|
Vance ; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
BLD-Final | 8/13/2004 | 8/16/2004 | 8/16/2004 | A | FAIL |
Lane Manuel
|
|
|
Vance ; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
FIRE-Final Inspection | 8/13/2004 | 8/13/2004 | 8/13/2004 | P | FAIL |
Rick Jackson
|
|
|
Vance ; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Couldn't gain entry - doors locked; called the above number with no answser 8/13/2004 4:38:48 PM
|