BLD-Conference | 1/30/2008 | 1/30/2008 | 1/30/2008 | P | CANC |
Mike Jordan
|
|
|
|
DOC - Permit Expired | 1/30/2008 | 1/30/2008 | 1/30/2008 | P | PASS |
Mike Jordan
|
|
|
All repairs were not made. Fed EX is no longer ocupies bldg space. Next tenant will have to comply prior to occ.
|
BLD-Aging Inspection | 6/18/2007 | 6/18/2007 | 6/18/2007 | | NR |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 10/6/2006 | 10/6/2006 | 10/12/2006 | | NR |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 7/27/2006 | 7/27/2006 | 7/27/2006 | | CANC |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 5/17/2006 | 5/17/2006 | 5/17/2006 | | NR |
Troy Cobbley
|
|
|
I left a correction notice with the man incharge at FED EX and showed him that the doors need sprinkler coverage below them. I also left a message for ART at Petra Construction about the same issues.
|
BLD-Final | 1/21/2005 | 1/24/2005 | 1/24/2005 | A | CANC |
Lane Manuel
|
|
|
Scheduled by a contractor via Hello! on 1/21/2005 at 2:00:38 PM. Contact: ###-####.
needs fire inp. approval 1/24/2005 11:13:41 AM
|
BLD-Final | 1/19/2005 | 1/20/2005 | 1/20/2005 | A | CANC |
Lane Manuel
|
|
|
Scheduled by a contractor via Hello! on 1/19/2005 at 12:49:40 PM. Contact: ###-####.
need fire insp. 1/20/2005 9:46:36 AM
|
BLD-Final | 1/20/2005 | 1/20/2005 | 1/20/2005 | P | CANC |
Lane Manuel
|
|
|
darrin -call 1st before insp --pending fire fn ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
failed the fire insp. To reschedule bldg final. 1/20/2005 3:22:55 PM
|
Code Occupancy Approval | 1/21/2005 | 1/20/2005 | 1/20/2005 | A | DONE |
Scott M.Brown
|
|
|
DOORS IN SO SIGNED FINAL (COLOR ON INSIDE OF DOORWAYS NOT DONE BECAUSE OF COLD WEATHER BUT ARE NOT A MAJOR ITEM INSIDE OF DOORWAY). 1/21/2005 8:45:19 AM
|
FIRE-Final Inspection | 1/20/2005 | 1/20/2005 | 1/20/2005 | P | NR |
Troy Cobbley
|
|
|
darrin -call 1st before insp ; Phone #: ###-#### This building has an alarm system that has not been finaled. The fire alarm contractor has been contacted by me personally about this several times over the past couple of years. I let Darrin know that there would be no inspections until the fire alarm system had been approved. 1/20/2005 3:45:25 PM
|