Description |
(THE NETWORK GROUP - PIONEER PLAZA - 1ST FLR - CORRIDOR EXTENSION) (12-21-04) THE LOBBY WAS NOT REQUIRED TO BE RATED AS A 1-HR CORRIDOR WHEN IT WAS FIRST CONSTRUCTED. SINCE THE LENGTH OF THE PROPOSED DEAD END WILL NOT EXCEED 20 FEET, THE LOBBY IS STILL NOT REQUIRED TO BE RATED AS A 1-HR CORRIDOR. DOORS ARE NOT REQUIRED TO BE RATED. This building is fire sprinklered to substitute for 1-hr fire-resistance rated construction of the building. To extend a lobby about 16 feet into an existing tenant space hallway located on the 1st floor of an existing 3 story building. An existing non-rated door with glass sidelight will be relocated. Work is to include a set of double doors installed in the wall of the new lobby extension. All work shall comply with the approved drawings and the plan review report on file. Within the remodel area, the location of fire sprinkler heads shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW**
|