BLD-Final | 7/15/2005 | 7/18/2005 | 7/18/2005 | A | PASS |
Tom Arcoraci
|
|
|
SCOTT; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok for perm occ
|
Permanent Occupancy | | 7/18/2005 | 7/18/2005 | | DONE |
|
|
|
|
FIRE-Final Inspection | 5/24/2005 | 5/24/2005 | 5/24/2005 | P | PASS |
Troy Cobbley
|
|
|
Life safety finaled
|
BLD-Final | 2/24/2005 | 2/25/2005 | 2/25/2005 | A | PART |
Lane Manuel
|
|
|
scott ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
temp. c of o ok 2/25/2005 11:40:38 AM
|
FIRE-Final Inspection | 2/24/2005 | 2/24/2005 | 2/24/2005 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given with Sam Rogers permission. A final will be given when the sprinkler pendant is added in the cooler which will be here in four weeks, 2/24/2005 1:50:31 PM
|
BLD-Final | 2/22/2005 | 2/23/2005 | 2/23/2005 | A | CANC |
Lane Manuel
|
|
|
scott --call 1st for access ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD-Final | 2/18/2005 | 2/22/2005 | 2/22/2005 | A | CANC |
Lane Manuel
|
|
|
scott; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
needs fire life/safety appr. 2/22/2005 10:38:06 AM
|
FIRE-Final Inspection | 2/22/2005 | 2/22/2005 | 2/22/2005 | P | FAIL |
Troy Cobbley
|
|
|
scott --call 1st for access ; Phone #: ###-####
Provide permanant address per review notes 4 and 5. Provide fire extinguisher per note 6. Replace painted sprinkler head at the rear door. Provide sticker at the main exit. Provide sprinkler head in the walk in cooler. Sprinkler work will require permit. 2/22/2005 12:17:26 PM
|