Permit Information
Permit NumberBLD05-00112
StatusFinaled
Name UNICO PROPERTIES
Site Address 101 S CAPITOL BLVD
Project NameUS BANK-2ND FLR
Customer Number 
ePlanReviewNo
Description
(US BANK - 2ND FLR - CONFERENCE ROOMS, RESTROOMS, ELEVATOR LOBBY) This building is required to be fire sprinklered because it is a high rise. To remodel conference rooms, to upgrade core restrooms to be accessible to the disabled, and to remodel the elevator lobby located on the 2nd floor of an existing high-rise building. The area of the entire 2nd story is about 14,520 square feet and the occupant load is about 221. Selective nonstructural demolition is also covered under this permit. Work is to include interior nonbearing walls, a relocated folding partition, suspended ceilings, gypsum board soffits, interior doors, finishes, and relocated plumbing fixtures. The fire sprinkler system, fire alarm system, and high-rise life safety systems (and the infrastructure supporting these systems) for the 2nd floor are regulated under the provisions of the 2000 IBC. These systems shall be upgraded throughout the entire floor to comply with current standards unless they are already compliant. If not already existing, fire-safing shall be installed at the perimeter of the 2nd floor between the floor and the spandrel glass. All work shall comply with the 2003 IBC, the 2000 IBC as noted in the upgrade agreements, approved drawings, and the plan review report on file. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final8/12/20058/16/20058/17/2005APASS
DetailsDave Hannah
Scheduled by a contractor via Hello! on 8/12/2005 at 2:34:58 PM. Contact: ###-####. ok for perm occ
FIRE-Final Inspection8/10/20058/12/20058/12/2005PPASS
DetailsTroy Cobbley
Life safety finaled
FIRE-Final Inspection6/1/20056/2/20056/2/2005AFAIL
DetailsForrest France
Provide max occupant load sign in confrence room, see note #13, provide current inspection tag on fire ext. in US bank suite copy room, provide approved door hardware on two doors in Racine suite 208.
BLD-Framing/Rough-in4/28/20054/28/20054/28/2005PPART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 4/28/2005 at 9:34:33 AM. Contact: ###-####. ceiling grid ok
BLD-Framing/Rough-in4/7/20054/7/20054/7/2005PPART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 4/7/2005 at 7:33:22 AM. Contact: ###-####. ok to cover elevator lobby and rest rooms 4/8/2005 8:14:03 AM
BLD-Framing/Rough-in3/30/20053/30/20053/30/2005PPART
DetailsTroy James
Scheduled by a contractor via Hello! on 3/30/2005 at 9:45:28 AM. Contact: ###-####. ok to cover interior walls upon approval from trades 3/30/2005 3:09:54 PM