BLD-Final | 8/25/2005 | 8/29/2005 | 8/29/2005 | A | PASS |
Jim Sly
|
|
|
darrin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore OK for Perm Occ. ():
|
Permanent Occupancy | | 8/29/2005 | 8/29/2005 | | DONE |
|
|
|
|
BLD-Final | 8/22/2005 | 8/24/2005 | 8/24/2005 | A | CANC |
Jim Sly
|
|
|
After 10:00 please////darrin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
FIRE-Final Inspection | 8/18/2005 | 8/22/2005 | 8/22/2005 | A | PASS |
Forrest France
|
|
|
Life safety is satisfactory, the main entry door manual flush bolts have been removed.
|
FIRE-Final Inspection | 7/12/2005 | 7/15/2005 | 7/15/2005 | P | FAIL |
Troy Cobbley
|
|
|
april; Phone #: ###-#### Still need to remove the manual flush bolts from the main exit. All other items corrected.
|
FIRE-Final Inspection | 7/5/2005 | 7/6/2005 | 7/6/2005 | A | FAIL |
Troy Cobbley
|
|
|
Repair all three exit signs, provide two emergency lights,one at the front and one at the back. Provide nonlocking hardware on the back door to short corridor. Provide one 2A10BC fire extinguisher with current inspection tag and mounted at 48" AFF. Remove thumbturn from main exit, keyed hardware is ok. Provide automatic flush bolts for the main exit. Provide "Door to remain unlocked when building is occupied" sticker at the main exit. Remove manual flush bolts from the rear door active leaf.
|
BLD-Final | 6/29/2005 | 7/1/2005 | 7/1/2005 | A | NR |
Jim Sly
|
|
|
please call 30 min prior to inspection///darrin; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa Need Fire final 1st
|