Permit Information
Permit NumberBLD05-01694
StatusFinaled
Name THORNTON-OLIVER KELLER
Site Address 3231 N COLE RD
Project NameCOLE VILLAGE
Customer Number 
ePlanReviewNo
Description
(NO TENANT-VANILLA FINISH)(COLE VILLAGE SHOPPING CENTER) To remodel a 12,317 sq.ft. unoccupied retail space at the south end of the shopping center per approved plans and DRH04-00250. Work to include, installation of new openings into existing CMU wall per engineering to install new storefronts and man door, new built out cornice with stucco finish, NO OCCUPANCY UNDER THIS PERMIT, a separate permit is required for occupancy. This building is fully fire sprinklered any alterations or modifications to the sprinkler system shall be per NFPA #13 as regulated by the fire department. Rmh
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final5/31/20065/31/20065/31/2006PPASS
DetailsJim Sly
###-#### - steve
BLD-Framing/Rough-in5/30/20065/30/20065/31/2006PPASS
DetailsJim Sly
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
C/C issued
DOC - Permit Finaled5/31/20065/31/20065/31/2006PPASS
DetailsJim Sly
FIRE-Final Inspection5/30/20065/30/20065/30/2006PPASS
DetailsTroy Cobbley
Life safety finaled
FIRE-Final Inspection5/23/20065/24/20065/24/2006AFAIL
DetailsTroy Cobbley
The insulation has not been fixed yet and there are two sheets of plywood in the rear of the store that are over 4' wide that need sprinkler coverage under.
BLD-Final1/23/20061/24/20061/24/2006ANR
DetailsJim Sly
Steve -- call 1st before insp; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
Need Fire to sign off B 4 Structural
FIRE-Final Inspection1/17/20061/19/20061/19/2006AFAIL
DetailsTroy Cobbley
Insulation is falling from the roof deck and obstructing the upright sprinkler heads. The sprinkler heads along the north wall are overspaced from the north wall and plywood attached to the bottom of the joists at the east wall create obstructions.
BLD-Framing/Rough-in11/10/200511/14/200511/14/2005APASS
DetailsJim Sly
steve ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
Note: Mentioned to contractor that at some point in time....possibly when new tenant improvement.....that the exposed kraft faced ceiling insulation should be protected. He mentioned to Mike Dalberg of Thorton/Oliver/Keller.
BLD-Framing/Rough-in10/13/200510/14/200510/14/2005PPART
DetailsJim Sly
steve--nailing insp --late pm??; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
Nailing on front sheathing OK (EXT cornice)
BLD-Framing/Rough-in10/12/200510/13/200510/13/2005APART
DetailsJim Sly
steve; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Front Exterior Cornice Trusses and framing OK
BLD-Foundation9/16/20059/19/20059/19/2005PPART
DetailsJim Sly
steve --rebar insp; Phone #: ###-#### Internet Inspection Request from: Marsha Smyl
5 Footings OK Pending special insp, tests and approvals from Terricon. NEXT TO ACE HARDWARE