BLD-Aging Inspection | 10/31/2005 | 10/31/2005 | 10/31/2005 | | PASS |
Tom Arcoraci
|
|
|
1-31-06
|
FIRE-Final Inspection | 8/31/2005 | 8/31/2005 | 8/31/2005 | P | PASS |
Forrest France
|
|
|
HVAC duct smoke detectors shut down units upon activation, fire life safety finaled.
|
FIRE-Final Inspection | 8/26/2005 | 8/26/2005 | 8/26/2005 | P | FAIL |
Forrest France
|
|
|
Two duct smoke detectors failed to shut down units upon activation, all other items are okay.
|
BLD-Final | 8/26/2005 | 8/26/2005 | 8/26/2005 | P | PASS |
Mike Jordan
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore. OK for perm occc when fire/life/safety has signed off.
|
FIRE-Final Inspection | 8/25/2005 | 8/25/2005 | 8/25/2005 | P | FAIL |
Forrest France
|
|
|
No power to HVAC units to enable testing of duct smoke detection devices, the remaining life safety issues are satisfactory.
|
BLD-Final | 8/25/2005 | 8/25/2005 | 8/25/2005 | P | FAIL |
Mike Jordan
|
|
|
jim pending fire fn ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie. Fire failed. restrooms not complete.
|
FIRE-Final Inspection | 8/19/2005 | 8/22/2005 | 8/22/2005 | P | NR |
Forrest France
|
|
|
Not ready for inspection, on site discussion with Jim regarding fire ext. locations, addressing, duct smoke remote annunciators, and door hardware.
|
BLD-Final | 8/18/2005 | 8/19/2005 | 8/19/2005 | A | CANC |
Tom Arcoraci
|
|
|
jim; Phone #: ###-#### Note: late morning Internet Inspection Request from: Cathy Chiles
|
BLD-Other | 8/19/2005 | 8/19/2005 | 8/19/2005 | P | PASS |
Tom Arcoraci
|
|
|
jim; Phone #: ###-#### Note: late morning Internet Inspection Request from: Cathy Chiles grid ok
|
BLD-Framing/Rough-in | 8/11/2005 | 8/12/2005 | 8/12/2005 | A | PART |
Tom Arcoraci
|
|
|
jim kaiser; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa office ok to need new details for bath rooms
|
BLD-Conference | 8/8/2005 | 8/8/2005 | 8/8/2005 | P | PASS |
Tom Arcoraci
|
|
|
jim kaiser; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|