Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberBLD06-00084
StatusFinaled
Name CITY OF BOISE
Site Address 150 N CAPITOL BLVD
Project NameCITY HALL
Customer Number 
ePlanReviewNo
Description
(City Hall - Bonneville Room)(3RD Floor) NO CONTRACTOR REISTRATION PROVIDED. APPLICANT CERTIFIES EXEMPTION PER IDAHO STATUTE 54-5205. To remodel an exising 990 sq ft conference room located on the third floor of City Hall per approved plans. Work to include, removal of nonbearing partition to expand this space approximately 104 sq ft, relocation desks and chairs, replace and install new 20-minute rated entry doors off of elevator lobby area, replace & install new 3'0" x 6'8" door off of city counsel chambers, installation of new door hardware, extend ceiling as needed and miscelaneous related finishes. This building is fully fire sprinklered and any alterations or modifications to the sprinkler system WILL require a separate permit. (rmh) POST OCCUPANT LOAD SIGN AT ( 66 )
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final4/18/20064/19/20064/20/2006PFAIL
DetailsDave Hannah
renea; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles needs to install doors and hardware
FIRE-Final Inspection4/18/20064/19/20064/19/2006APASS
DetailsForrest France
Fire life safety is acceptable pending installation of lever hardware at two door locations.
BLD-Final4/10/20064/11/20064/11/2006AFAIL
DetailsDave Hannah
renea; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles needs fire sign off
FIRE-Final Inspection4/10/20064/10/20064/10/2006PFAIL
DetailsForrest France
Max occupant load sign is not yet posted, approved plans and sign off card not available on site.
BLD-Final4/3/20064/3/20064/4/2006PCANC
DetailsDave Hannah
-- ###-####-- renee--pending fire fn & ele
FIRE-Final Inspection4/3/20064/3/20064/3/2006PNR
DetailsForrest France
Door hardware at two locations is not installed yet, missing fire sprinkler escutcheon at closet, need to post max. occupant load sign as discussed, ceiling tile is not installed at relocated heads.
BLD-Framing/Rough-in3/23/20063/24/20063/24/2006APASS
DetailsTom Arcoraci
renea; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
FIRE-Conference2/16/20062/17/20062/17/2006ADONE
DetailsForrest France
On site confrence to discuss construction modifications that may affect fire sprinkler coverage. Two locations at the west side will require changes in sprinkler coverage to avoid "cold solder" of heads that are now located too close together due to wall removal. A fire sprinkler permit is necessary to perform this work.
BLD-Framing/Rough-in2/14/20062/14/20062/15/2006PPASS
DetailsDave Hannah
RENE; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie