BLD-Final | 10/12/2006 | 10/13/2006 | 10/13/2006 | A | PASS |
Jim Storey
|
|
|
darren; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
DOC - Permit Finaled | 10/13/2006 | 10/13/2006 | 10/13/2006 | P | PASS |
Jim Storey
|
|
|
|
FIRE-Final Inspection | 10/11/2006 | 10/12/2006 | 10/12/2006 | A | PASS |
Forrest France
|
|
|
C/N items are complete, final life safety inspection is satisfactory.
|
BLD-Final | 10/6/2006 | 10/9/2006 | 10/10/2006 | P | NR |
Jim Storey
|
|
|
darin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
FIRE-Final Inspection | 10/6/2006 | 10/9/2006 | 10/9/2006 | A | FAIL |
Forrest France
|
|
|
One damper on the north side is non functional due to a smoke head equipment failure, need to repair and test prior to final.
|
FIRE-Final Inspection | 10/2/2006 | 10/3/2006 | 10/3/2006 | A | NR |
Forrest France
|
|
|
In duct smoke detectors at two locations are not yet completed, no inspection performed.
|
FIRE-Conference | 9/12/2006 | 9/13/2006 | 9/13/2006 | A | DONE |
Forrest France
|
|
|
On site confrence to discuss f/s dampers at the 2nd floor corridor and requirements for in duct detectors.
|
BLD-Framing/Rough-in | 9/11/2006 | 9/11/2006 | 9/11/2006 | P | FAIL |
Jim Storey
|
|
|
darren; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley need s/f damper at 2 nd floor coridor wall.
|