Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberBLD06-01943
StatusFinaled
Name THORNTON-OLIVER KELLER
Site Address 671 E RIVERPARK LN Unit: 200
Project NameRIVER RUN BLDG F
Customer Number 
ePlanReviewNo
Description
HC COMPANY INC RCE- 793 //(MWH AMERICAS INC - RIVER RUN BLDG F - STE 200) To remodel the existing 8,190 sq. ft. second floor to create three separate suites with upgrade of existing 1-hour corridor exit system to meet requirements of code (UBC) under which originally constructed. This permit is for creation and remodel of a 3,648 sq.ft. area for office use by MWH Americas, Inc., on the 2nd floor. To perform selective interior demolition. Work includes upgrade construction and relocating portion of 1-hour rated corridor wall and verify all other portions of rated corridor comply with UBC provisions under which constructed; to protect openings, repair 1-hour tunnel ceiling and firestop, fire/smoke dampers duct penetrations per UBC under which installed for that portion off the perimeter wall for this new suite made up by the corridor wall. The layout of this existing area and use are virtually unchanged for last plans of record, except for relocating within existing ceiling of rooms the HVAC & lighting to remain as-is. Two exits are required and 2 exist. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final10/12/200610/13/200610/13/2006APASS
DetailsJim Storey
darren; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
DOC - Permit Finaled10/13/200610/13/200610/13/2006PPASS
DetailsJim Storey
FIRE-Final Inspection10/11/200610/12/200610/12/2006APASS
DetailsForrest France
C/N items are complete, final life safety inspection is satisfactory.
BLD-Final10/6/200610/9/200610/10/2006PNR
DetailsJim Storey
darin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
FIRE-Final Inspection10/6/200610/9/200610/9/2006AFAIL
DetailsForrest France
One damper on the north side is non functional due to a smoke head equipment failure, need to repair and test prior to final.
FIRE-Final Inspection10/2/200610/3/200610/3/2006ANR
DetailsForrest France
In duct smoke detectors at two locations are not yet completed, no inspection performed.
FIRE-Conference9/12/20069/13/20069/13/2006ADONE
DetailsForrest France
On site confrence to discuss f/s dampers at the 2nd floor corridor and requirements for in duct detectors.
BLD-Framing/Rough-in9/11/20069/11/20069/11/2006PFAIL
DetailsJim Storey
darren; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley need s/f damper at 2 nd floor coridor wall.