FIRE-Final Inspection | 7/9/2008 | 7/10/2008 | 7/10/2008 | A | PASS |
Forrest France
|
|
|
Fire life safety final inspection passed, correction notice items are finished.
|
FIRE-Final Inspection | 7/2/2008 | 7/3/2008 | 7/3/2008 | A | FAIL |
Forrest France
|
|
|
Smoke alarms at units 2235, 2243 and 2249 are in need of adjustment due to spacing requirements not met per NFPA 72 ch. 11 including proximity to bathroom doors, HVAC registers, spacing outside of sleeping areas, one missing smoke alarm. See fire code review notes attatched to the approved plan set for details. Remainder of fire life safety issues are acceptable.
|
FIRE-Final Inspection | 7/1/2008 | 7/2/2008 | 7/2/2008 | A | DEFR |
Forrest France
|
|
|
AM inspections overbooked, contractor rescheduled for 7/3 per agreement.
|
FIRE-Final Inspection | 5/14/2008 | 5/15/2008 | 5/15/2008 | A | FAIL |
Forrest France
|
|
|
Need approved plans and fire code review notes available on site, missing knox box, per contractor no fire extinguishers have been provided, lacking vehicle impact protection at the three new hydrants due to incomplete site work/curbing, will need access to each unit to test smoke alarms.
|
BLD-Final | 5/9/2008 | 5/9/2008 | 5/9/2008 | A | PASS |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 5/9/2008 at 1:37:58 AM. Contact: ###-####. ok for perm occ
verified that all trades have been signed off _ Dave Hannah did a fn insp--per Bob Archibald do not need to print an Occ card..just note it in screen-BAS
|
Code Occupancy Approval | | | 4/23/2008 | | DONE |
|
|
|
Landscaping and lot striping meets requirements
|
BLD-Conference | 3/25/2008 | 3/25/2008 | 3/25/2008 | A | DONE |
Forrest France
|
|
|
Project related fire alarm and sprinkler permits are complete, occupancy approval pending satisfactory fire life safety inspection-see fire code review notes attatched to the stamped plan set for requirements and conditions.
|
BLD-Energy code compliance | 7/9/2007 | 7/9/2007 | 7/9/2007 | P | DEFR |
Mike Jordan
|
|
|
steve; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang. No time.
|
BLD-Energy code compliance | 7/5/2007 | 7/6/2007 | 7/6/2007 | P | NR |
Tom Arcoraci
|
|
|
steve Phone #: ###-####
|
BLD-Framing/Rough-in | 7/3/2007 | 7/5/2007 | 7/5/2007 | P | PASS |
Jim Storey
|
|
|
steve; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
|
BLD-Energy code compliance | 6/19/2007 | 6/19/2007 | 6/19/2007 | P | PART |
Dave Hannah
|
|
|
steve; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok to cover the west five units
|
BLD-Framing/Rough-in | 6/15/2007 | 6/15/2007 | 6/15/2007 | A | PART |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 6/15/2007 at 6:25:49 AM. Contact: ###-####. west fire units ok to insulate
|
BLD-Foundation | 1/8/2007 | 1/9/2007 | 1/8/2007 | A | PART |
Dave Hannah
|
|
|
steve ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to pour east half
|
BLD-Foundation | 1/3/2007 | 1/4/2007 | 1/4/2007 | A | PART |
Dave Hannah
|
|
|
steve - late morning ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith west half ok to pour
|
BLD-Footing | 12/27/2006 | 12/28/2006 | 12/28/2006 | A | PART |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 12/27/2006 at 9:30:48 PM. Contact: ###-####. east half ok to pour
|
BLD-Footing | 12/18/2006 | 12/19/2006 | 12/19/2006 | A | PART |
Dave Hannah
|
|
|
Steve Note: would like insp around 11 am; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett west half
|