BLD-Final | 1/24/2007 | 1/25/2007 | 1/25/2007 | A | PASS |
Mike Jordan
|
|
|
jeff; Phone #: ###-#### Internet Inspection Request from: Victoria Beall. Ok for perm occ. letter of compliance was issued for shell and core portion as well.
|
Permanent Occupancy | | 1/25/2007 | 1/25/2007 | | DONE |
|
|
|
|
BLD-Final | 12/27/2006 | 12/28/2006 | 12/28/2006 | A | PART |
Mike Jordan
|
|
|
jeff ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith. ok for temp occ. Shell and core was inspected also and was given temp. TI will be ok for perm occ once shell goes perm. No sign off cards!!!
|
BLD-Final | 12/26/2006 | 12/27/2006 | 12/27/2006 | P | FAIL |
Mike Jordan
|
|
|
jeff ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith. Needs to get elec. finaled.
|
FIRE-Final Inspection | 12/26/2006 | 12/27/2006 | 12/27/2006 | A | PASS |
Troy Cobbley
|
|
|
Life safety finaled
|
FIRE-Final Inspection | 12/22/2006 | 12/26/2006 | 12/26/2006 | A | FAIL |
Forrest France
|
|
|
The sample tube for the duct detector is not approved, provide the correct length tube and means for testing at next inspection, remaining life safety issues are okay.
|
FIRE-Final Inspection | 12/22/2006 | 12/22/2006 | 12/22/2006 | P | CANC |
Troy Cobbley
|
|
|
Per Jeff he wants to reschedule for next week.
|
FIRE-Final Inspection | 12/20/2006 | 12/21/2006 | 12/21/2006 | P | FAIL |
Troy Cobbley
|
|
|
Lower fire extinguishers, provide the correct remote annunciator for the duct smoke detector and the correct sample tube.
|
BLD-Conference | 11/7/2006 | 11/7/2006 | 11/7/2006 | P | PASS |
Mike Jordan
|
|
|
jeff ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith. framing at 1hr ceiling. ok for 2nd layer. exterior 1hr wall interior side ok.
|
BLD-Energy code compliance | 11/6/2006 | 11/6/2006 | 11/6/2006 | P | PASS |
Mike Jordan
|
|
|
jeff ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith. All framing issues have been resoloved.
|
BLD-Energy code compliance | 11/3/2006 | 11/6/2006 | 11/6/2006 | A | NH |
Mike Jordan
|
|
|
jeff; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. Shaft is being repaired, firecaulking not complete.
|
BLD-Conference | 11/2/2006 | 11/3/2006 | 11/3/2006 | A | PART |
Mike Jordan
|
|
|
jeff ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith. Still needs to complete firew caulking build shaft correctly, and box out ele. panel. All other issues have been resolved. ok to insul. Contractor to repair and call back for insp.
|
BLD-Framing/Rough-in | 11/2/2006 | 11/2/2006 | 11/2/2006 | P | NR |
Mike Jordan
|
|
|
jeff ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
BLD-Framing/Rough-in | 11/1/2006 | 11/1/2006 | 11/1/2006 | P | FAIL |
Mike Jordan
|
|
|
jeff; Phone #: ###-#### Internet Inspection Request from: Patricia Smith. Needs to remove roof vents next to property line wall. complete all fire caulking. double layer can lights. c/n posted
|
BLD-Framing/Rough-in | 10/27/2006 | 10/30/2006 | 10/30/2006 | A | NR |
Mike Jordan
|
|
|
kameron; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. Mech ri insp failed. Elec permit for this TI is attached to shell permit.
|