Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberBLD06-03451
StatusFinaled
Name LUEKENGA CONSTRUCTION INC
Site Address 5900 W CASTLE DR
Project NameLDS CHURCH
Customer Number 
ePlanReviewNo
Description
To remodel the exisitng church building with new interior doors, new mechanical room created on the second floor, new ceilings in limited areas, new partitions, new mechanical systems with related electrical, plumbing and fire alarm work per plans. Permit includes all demo to prepare for remodel. (NO CONTRACTOR REGISTRATION PROVIDED. APPLICANT CERTIFIES EXEMPTION PER IDAHO STATUE 54-5205) (LDS CHURCH - REMODEL) Records show this building as a Type V-1hr
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final11/29/200711/30/200711/30/2007PPASS
DetailsTony Young
Scheduled by a contractor via Hello! on 11/29/2007 at 8:04:43 AM. Contact: ###-####.
DOC - Permit Finaled11/30/200711/30/200711/30/2007PPASS
DetailsTony Young
BLD-Conference8/13/20078/13/20078/13/2007APART
DetailsTony Young
Tony , please meet Dixie for a conference at 9am on this job.
met w/ 411 and engineer on mech issues,, fire dampers, listings on same,, fixes due to 4th angle missing and round holes in floor/ ceiling assembly w/ square ducts, etc,, eng will try to get listings,, or fixes to comply
BLD-Framing/Rough-in8/2/20078/3/20078/3/2007PPASS
DetailsDave Hannah
steven Note: 1st thing in afternoon - they leave at 3:30 please contact Phone #: ###-#### two mec chases ground level corr and ceiling upstairs corr ok to cover
BLD-Conference7/2/20077/3/20077/3/2007APASS
DetailsTony Young
steven; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
?s about roof deck vent,, 16 ga metal ok for small void
BLD-Conference5/4/20075/7/20075/7/2007APART
DetailsTony Young
conference with dixie and gary of owyhee sheet metal regarding fire dampers ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
met w/ 411 on smoke/fire damper,, need to do as plans say,, one at floor level and one at corridor wall
BLD-Conference4/13/20074/17/20074/17/2007ADONE
DetailsJim Sly
Stephen 10:00; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
Call Jim Sly for details ###-####