Information based on query as of Friday, June 28, 2024.
Permit Information
Permit NumberBLD06-03528
StatusFinaled
Name MCALVAIN CONSTRUCTION INC
Site Address 1112 W MAIN ST Unit: 5TH FLR
Project NameROYAL PLAZA
Customer Number 
ePlanReviewNo
Description
(ROYAL PLAZA - ANDREA CONDOS - 5TH STORY CORRIDOR) To construct a 1,461 square foot 1-hr fire-resistance-rated egress corridor system to serve residential condominium units located on the 5th story of a high-rise building. Work is to include 1-hr fire-resistance-rated corridor walls, corridor doors having a fire-protection-rating of 20 minutes, suspended ceilings, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection6/1/20106/1/20106/1/2010 PASS
DetailsDave Hannah
DOC - Permit Finaled6/1/20106/1/20106/1/2010PPASS
DetailsDave Hannah
FIRE-Final Inspection2/27/20082/28/20082/28/2008APASS
DetailsForrest France
Fire life safety finaled.
BLD-Final1/22/20081/22/20081/25/2008PPART
DetailsDave Hannah
todd Phone #: ###-#### ok for use ok to final after two hour fire rated infill wall on east wall also needs shell and core finaled this is all been aproved by Bruce D Chatterton and Legal and an Agreement with Bob Hosac
FIRE-Final Inspection1/22/20081/22/20081/22/2008PPART
DetailsForrest France
Repair one EM light at the east exit corridor between units 501 and 502, one missing door installed while on site, missing smoke seal at the laundry chute door, remainder of life safety is acceptable, final pending shell and core building permit final.
BLD-Final1/8/20081/8/20081/8/2008PNR
DetailsDave Hannah
Tod; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
BLD-Final1/4/20081/8/20081/8/2008ANR
DetailsDave Hannah
Tod; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
FIRE-Final Inspection1/4/20081/7/20081/7/2008AFAIL
DetailsForrest France
Missing inspections and permit finals for the fire sprinkler and alarm work associated with this building permit number.
BLD-Framing/Rough-in8/28/20078/28/20078/29/2007PPASS
DetailsDave Hannah
Jerry; Phone #: ###-#### Internet Inspection Request from: Hattie James
BLD-Aging Inspection7/18/20077/18/20077/18/2007 PASS
DetailsDave Hannah
wip