FIRE-Final Inspection | 9/13/2007 | 9/14/2007 | 9/14/2007 | A | PASS |
Forrest France
|
|
|
All items on the previously issued correction notice have been completed, final fire life safety inspection passed.
|
FIRE-Final Inspection | 6/22/2007 | 6/25/2007 | 6/25/2007 | A | FAIL |
Forrest France
|
|
|
See correction notice left on site for items including provision of approved door hardware at three marked exits, provide current annual inspection for the existing fire sprinkler system, re-attatch one PFE to column #1, the newly installed deck to floor partition at the SE corner of the warehouse disrupts required fire sprinkler system coverage and density, no racking allowed over 8' in height without a separate application and permit, see fire code review notes and approved plans for details and locations of defficiencies.
|
BLD-Final | 6/21/2007 | 6/22/2007 | 6/22/2007 | A | PASS |
Jim Storey
|
|
|
russ Phone #: ###-####
|
BLD-Final | 6/14/2007 | 6/15/2007 | 6/15/2007 | A | FAIL |
Jim Storey
|
|
|
russ - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
BLD-Aging Inspection | 5/29/2007 | 5/29/2007 | 5/29/2007 | | NR |
Jim Storey
|
|
|
no call for insp. outstanding plm permit.
|