BLD-Final | 1/25/2008 | 1/25/2008 | 1/25/2008 | P | PASS |
Tony Young
|
|
|
Phone #: ###-#### ok for perm cof o
|
BLD-Conference | 9/21/2007 | 9/21/2007 | 9/21/2007 | P | PASS |
Tony Young
|
|
|
phillip Phone #: ###-#### ok for temp occ.
|
BLD-Final | 9/20/2007 | 9/20/2007 | 9/20/2007 | P | CANC |
Tony Young
|
|
|
Wayne; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt Inspection cancelled from web by: Barbara Stitt
|
BLD-Final | 8/31/2007 | 9/4/2007 | 9/4/2007 | A | FAIL |
Tony Young
|
|
|
Phillip; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt c/n posted,, ok for temp. occ.
|
FIRE-Final Inspection | 8/31/2007 | 8/31/2007 | 8/31/2007 | P | PASS |
Forrest France
|
|
|
Fire life safety final inspection passed.
|
FIRE-Final Inspection | 8/22/2007 | 8/23/2007 | 8/23/2007 | A | FAIL |
Troy Cobbley
|
|
|
Need to provide remote annunciator as per the IMC. Shutdown did test ok and the enclosure has been provided. All other items are ok.
|
FIRE-Final Inspection | 8/21/2007 | 8/21/2007 | 8/21/2007 | P | FAIL |
Forrest France
|
|
|
Need to provide weatherproof enclosure for the roof mounted duct detector and provide means for functionality testing.
|
FIRE-Final Inspection | 8/17/2007 | 8/17/2007 | 8/17/2007 | P | DEFR |
Forrest France
|
|
|
To be rescheduled pending HVAC issues.
|
BLD-Final | 8/13/2007 | 8/15/2007 | 8/15/2007 | P | CANC |
Tony Young
|
|
|
phill Phone #: ###-####
|
BLD-Footing | 8/14/2007 | 8/14/2007 | 8/14/2007 | P | CANC |
Tony Young
|
|
|
Mike wrong permit
|
BLD-Conference | 8/10/2007 | 8/13/2007 | 8/13/2007 | A | PART |
Tony Young
|
|
|
phillip Phone #: ###-#### conf on final
|
FIRE-Final Inspection | 8/10/2007 | 8/13/2007 | 8/13/2007 | A | NR |
Forrest France
|
|
|
Missing address numbers, door hardware, see fire code review notes for general requirements.
|
BLD-Final | 8/9/2007 | 8/13/2007 | 8/13/2007 | P | CANC |
Tony Young
|
|
|
Philip ; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
BLD-Framing/Rough-in | 7/16/2007 | 7/16/2007 | 7/16/2007 | P | PASS |
Tony Young
|
|
|
phillip Phone #: ###-####
|
BLD-Framing/Rough-in | 7/12/2007 | 7/13/2007 | 7/13/2007 | P | PASS |
Dave Hannah
|
|
|
PHILLIP Phone #: ###-####
|