BLD-Final | 7/31/2007 | 8/2/2007 | 8/2/2007 | P | PASS |
Dave Hannah
|
|
|
dave; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok for perm occ
|
FIRE-Final Inspection | 7/25/2007 | 7/26/2007 | 7/26/2007 | A | PASS |
Forrest France
|
|
|
Fire life safety is acceptable pending repair of one "sticking" door leaf at the east exit pair of doors, existing service doors at the 1st floor kitchen area to be replaced during building upgrade in process per tenant and general contractor.
|
BLD-Final | 7/23/2007 | 7/25/2007 | 7/25/2007 | P | NR |
Dave Hannah
|
|
|
dave Phone #: ###-#### needs other trades to final
|
FIRE-Final Inspection | 7/23/2007 | 7/25/2007 | 7/25/2007 | A | NR |
Forrest France
|
|
|
Need project related fire sprinkler permit final prior to life safety final.
|
BLD-Conference | 7/17/2007 | 7/18/2007 | 7/18/2007 | A | CANC |
Dave Hannah
|
|
|
dave - pls call 30 mins prior; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang postphone intil further notice dave
|
BLD-Framing/Rough-in | 7/9/2007 | 7/10/2007 | 7/10/2007 | A | PASS |
Dave Hannah
|
|
|
dave; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang met with arch and cont on site ok to stablize wall with cross rods
|
BLD-Framing/Rough-in | 7/6/2007 | 7/9/2007 | 7/9/2007 | A | FAIL |
Tony Young
|
|
|
dave Phone #: ###-#### part ok,, need to add 3x3 posts per plan, or get change from architect,, ok to cover unaffected areas
|
FIRE-Conference | 7/6/2007 | 7/9/2007 | 7/9/2007 | A | DONE |
Troy Cobbley
|
|
|
I went over life safety requiements with dave which included the placement of exit signs and emergency lights.
|