BLD-Final | 10/3/2007 | 10/4/2007 | 10/4/2007 | A | PASS |
Mike Jordan
|
|
|
don Phone #: ###-####. ok for perm occ. All issues resolved.
|
BLD-Final | 9/26/2007 | 9/27/2007 | 9/27/2007 | A | CANC |
Mike Jordan
|
|
|
ryan Phone #: ###-####. Cancelled by contractor via phone call.
|
BLD-Final | 9/25/2007 | 9/26/2007 | 9/26/2007 | P | PART |
Mike Jordan
|
|
|
don or ryan Phone #: ###-####. ok for temp occ. Need counter to meet ADA requirements. Needs to firecaulk sink drain line and provide listing for access door in bathroom at 1 hr. wall.
|
FIRE-Final Inspection | 9/25/2007 | 9/26/2007 | 9/26/2007 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
FIRE-Final Inspection | 9/24/2007 | 9/25/2007 | 9/25/2007 | A | FAIL |
Troy Cobbley
|
|
|
Missing two exit lights,fire extinguisher needs to be put up, emergency light in back store room not working.
|
BLD-Final | 9/24/2007 | 9/24/2007 | 9/24/2007 | P | CANC |
Mike Jordan
|
|
|
Don; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|
BLD-Other | 9/24/2007 | 9/24/2007 | 9/24/2007 | P | PASS |
Mike Jordan
|
|
|
Don; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt. grid ok. Need to check penetrations in restroom on final.
|
BLD-Framing/Rough-in | 8/31/2007 | 9/4/2007 | 9/4/2007 | P | PART |
Mike Jordan
|
|
|
don; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt. Needs to finish 1hr envelope at restroom, and compltete firestop. Framing at soffit ok.
|
BLD-Framing/Rough-in | 8/23/2007 | 8/24/2007 | 8/24/2007 | P | PASS |
Mike Jordan
|
|
|
don Phone #: ###-####. Interior framed walls only, no grid. Need UL specs for firecaulking on penetrations and still need to inspect 5/8 type x attachment.
|