FIRE-Final Inspection | 3/7/2008 | 3/7/2008 | 3/7/2008 | P | PASS |
Forrest France
|
|
|
Life safety final inspection passed.
|
BLD-Final | 3/7/2008 | 3/7/2008 | 3/7/2008 | P | PASS |
Tom Arcoraci
|
|
|
HENRY Phone #: ###-####
|
FIRE-Conference | 3/6/2008 | 3/7/2008 | 3/7/2008 | A | DONE |
Forrest France
|
|
|
Items on the issued correction notice are complete, need to remove the manual flush bolt at one door leaf from the theatre area and provide verbage on the load signs indicating "max occupancy".
|
FIRE-Final Inspection | 3/7/2008 | 3/7/2008 | 3/7/2008 | P | CANC |
Forrest France
|
|
|
Life safety final please.
|
BLD-Final | 1/11/2008 | 1/14/2008 | 1/14/2008 | P | NR |
Tom Arcoraci
|
|
|
Henry Phone #: ###-####
|
FIRE-Final Inspection | 1/11/2008 | 1/14/2008 | 1/14/2008 | A | FAIL |
Forrest France
|
|
|
See seven item correction notice left on site for a list of defficiencies including door hardware at four locations, repair EM lighting, install cover at open j-box, missing two max. occupant load signs, post one PFE, provide an additional exit sign per plan review annotations, post signage at the main exit from the basement club area, see building plan review notes for general requirements.
|