Permit Information
Permit NumberBLD08-00020
StatusExpired
Name CSDI CONSTRUCTION INC
Site Address 8460 W EMERALD ST
Project NameGOLDEN CORRAL
Customer Number 
ePlanReviewNo
Description
Relocate an existing Type 1 Hood system and reuse the existing grease duct. Construct aprox. 10 ln ft of non conbustable wall in back and side of relocated hood. Maintane shaft duct wrap protection of grease duct. FIRE PERMITS FOR HOOD AND ALARM WORK WILL BE REQUIRED THRU THE FIRE PLAN REVIEW. 301
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection6/15/20106/15/20106/15/2010 DONE
DetailsMike Jordan
DOC - Permit Expired6/15/20106/15/20106/15/2010PPASS
DetailsMike Jordan
All trades were finaled. No occupancy required. Permit is expired.
FIRE-Final Inspection7/30/20097/31/20097/31/2009APASS
DetailsTroy Cobbley
Lif safety passed. The hood suppression system operated correctly and reported to the fire alarm panel.
FIRE-Final Inspection7/9/20097/10/20097/10/2009AFAIL
DetailsTroy Cobbley
The power under both hoods did not shutoff and the cable actuater did not actuate.
FIRE-Final Inspection5/11/20095/12/20095/12/2009AFAIL
DetailsTroy Cobbley
This inspection was actually for a conference. Mike and I went over items that I would need for the final inspection which included a copy of the approved drawings and testing the relocated hood.
BLD-Framing/Rough-in2/11/20082/12/20082/12/2008APASS
DetailsMike Jordan
gale Phone #: ###-####. Interior steel stud wall for new type 1 hood. ok to cover.