Information based on query as of Wednesday, August 14, 2024.
Permit Information
Permit NumberBLD08-00547
StatusExpired
Name BLACK HORSE CONSTRUCTION
Site Address 305 N STEELHEAD WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
(NO TENANT - VANILLA SPACE) To remodel a 31,263 sq.ft. previously occupied warehouse by installing demising partitions to divide into 3 unoccupied areas per approved plans. This space is at the east end and will be 15,619 sq.ft. No new heating, plumbing or electrical under this permit. Existing rooms include 2 nonaccessible restrooms, 1 accessible restroom, 1 janitor's closet with floor sink. Previous tenant constructed under BLD05-00574. NO OCCUPANCY ALLOWED UNDER THIS PERMIT a separate permit will be required to occupy this space. This building is fully fire sprinklered for area increase. ANY ALTERATIONS TO THE SPRINKLER SYSTEM & FIRE ALARM SYSTEM WILL require separate permits, and shall be installed and maintained per NFPA #13 as regulated by the fire department. (SRZ)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection11/24/201011/24/201011/24/2010 CANC
DetailsMike Jordan
DOC - Permit Expired11/24/201011/24/201011/24/2010PPASS
DetailsMike Jordan
FIRE-Final Inspection8/1/20088/4/20088/4/2008AFAIL
DetailsTroy Cobbley
The racking permit still needs to be provided, the duct detector and fire alarm panel are still in a trouble condition as per the original correction notice. The other items have been corrected.
FIRE-Final Inspection4/24/20084/25/20084/25/2008AFAIL
DetailsTroy Cobbley
Inspection was for units 305 and 357. Repair exit signs/emergency lights in both tenants. Provide annual inspection for the fire extinguishers in both tenants. Provide additional fire extinguisher near front (south end) of tenant 357. Sprinkler pendants are overspaced off of the south wall in the two existing offices of tenant 357(see approved plans). Repair the damaged electrical outlests. Provide sprinkler coverage beneath the south overhead door of tenant 357 because the door exceeds 4'-0". Remove the thumbturn locks from the restroom doors in tenant 305. Provide a racking permit for the 11'-6" racks located in tenant 305. Currently balloons, refrigerators, computers and toys (plastic) are being stored on wooden pallets within (floor level) the racks themselves. Storage is at 7'-0". Atleast two building columns have been positionded within the storage racks which requires sprinkler protection per NFPA 13. The duct smoke detectors in unit 305 are in a trouble condition and will need repaired. The fire alarm panel is in a trouble condition and will need repaired. Provide approved hardware on the south secondary exit door from tenant 305. Provide corrected upright fire sprinkler protection along both sides of the two new full height walls. Both sides of walls to be included.
BLD-Framing/Rough-in4/15/20084/16/20084/16/2008APASS
DetailsMike Jordan
mark Phone #: ###-####. Interio demissing wall.