Permit Information
Permit NumberBLD08-00549
StatusExpired
Name BLACK HORSE CONSTRUCTION
Site Address 357 N STEELHEAD WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
NO TENANT - VANILLA SPACE) To remodel a 31,263 sq.ft. previously occupied warehouse by installing demising partitions to divide into 3 unoccupied areas per approved plans. This space is at the west end and will be 9,806sq.ft. No new heating, plumbing or electrical under this permit. Existing rooms include 2 nonaccessible restroom. Previous tenant constructed under BLD05-00574. NO OCCUPANCY ALLOWED UNDER THIS PERMIT, a separate permit will be required to occupy this space. This building is fully fire sprinklered for area increase. ANY ALTERATIONS TO THE SPRINKLER SYSTEM & FIRE ALARM SYSTEM WILL require separate permits, and shall be installed and maintained per NFPA #13 as regulated by the fire department. (SRZ)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection1/12/20111/12/20111/14/2011 CANC
DetailsMike Jordan
DOC - Permit Expired1/14/20111/14/20111/14/2011PPASS
DetailsMike Jordan
Permit is expired. For vanilla finish only.
FIRE-Final Inspection8/1/20088/4/20088/4/2008AFAIL
DetailsTroy Cobbley
The exit sign at teh north exit door has not been repaired, the fire extinguishers have not been tagged and the additional fire extinguisher at the south entrance has not been provided as per the original correction notice. All other life safety items have been corrected.
FIRE-Final Inspection4/24/20084/25/20084/25/2008AFAIL
DetailsTroy Cobbley
ScheInspection was for units 305 and 357. Repair exit signs/emergency lights in both tenants. Provide annual inspection for the fire extinguishers in both tenants. Provide additional fire extinguisher near front (south end) of tenant 357. Sprinkler pendants are overspaced off of the south wall in the two existing offices of tenant 357(see approved plans). Repair the damaged electrical outlests. Provide sprinkler coverage beneath the south overhead door of tenant 357 because the door exceeds 4'-0". Remove the thumbturn locks from the restroom doors in tenant 305. Provide a racking permit for the 11'-6" racks located in tenant 305. Currently balloons, refrigerators, computers and toys (plastic) are being stored on wooden pallets within (floor level) the racks themselves. Storage is at 7'-0". Atleast two building columns have been positionded within the storage racks which requires sprinkler protection per NFPA 13. The duct smoke detectors in unit 305 are in a trouble condition and will need repaired. The fire alarm panel is in a trouble condition and will need repaired. Provide approved hardware on the south secondary exit door from tenant 305. Provide corrected upright fire sprinkler protection along both sides of the two new full height walls. Both sides of walls to be included.duled by a contractor via Hello! on 4/24/2008 at 4:32:29 PM. Contact: ###-####.
BLD-Framing/Rough-in4/16/20084/16/20084/16/2008APASS
DetailsMike Jordan
Interior demissing wall.