BLD-Framing/Rough-in | 7/16/2009 | 7/16/2009 | 7/17/2009 | P | DONE |
Dave Hannah
|
|
|
sandra Phone #: ###-####
|
BLD-Final | 7/17/2009 | 7/17/2009 | 7/17/2009 | P | PASS |
Dave Hannah
|
|
|
sandra Phone #: ###-#### ok for perm occ
|
FIRE-Final Inspection | 7/13/2009 | 7/14/2009 | 7/14/2009 | A | PASS |
Troy Cobbley
|
|
|
life safety passed per stephanie cobbley
|
FIRE-Final Inspection | 7/9/2009 | 7/9/2009 | 7/10/2009 | P | FAIL |
Forrest France
|
|
|
Three items on the correction notice remain to be completed including hardware at the second storefront exit, signage at the back exit, remove the curtain from the path of egress.
|
FIRE-Final Inspection | 6/12/2009 | 6/12/2009 | 6/12/2009 | P | FAIL |
Troy Cobbley
|
|
|
Mount fire extinguisher at new kitchen with current inspection tag. Repair exit sign at east front door. Provide emergency lighting on pottery side of tenant. Remove curtain so that second exit can be seen. Provide exit sign to the rear exit as shown on the approved plans. Remove key lock from the kitchen side exit door. Repair emergency light on kitchen side of tenant.
|