Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberBLD09-00858
StatusFinaled
Name XPEDX
Site Address 432 N STEELHEAD WAY
Project NameXPEDX
Customer Number 
ePlanReviewNo
Description
**(XPEDX)** Application for inspection to determine requirements for issuance of a Certificate of Occupancy for an existing 23,111 square foot office / warehouse building. NO NEW WORK IS AUTHORIZED UNDER THIS PERMIT. This space was created under Building Permit #8553 (This permit is from ADA county, The building was built in 1979 and annexed into Boise City Dec 30, 1987). There are no changes to occupancy or use under this permit. TLW
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final9/22/20099/22/20099/22/2009PCANC
DetailsMike Jordan
BLD-Final9/21/20099/22/20099/22/2009APASS
DetailsMike Jordan
marilyn Phone #: ###-#### x 231. All outstanding items have been repaired. Ok for perm occ.
FIRE-Final Inspection9/21/20099/21/20099/22/2009PPASS
DetailsTroy Cobbley
Life safety passed. Per Mark Sentenno a racking permit will not be required. All other items have been addressed.
FIRE-Conference7/1/20097/2/20097/2/2009APASS
DetailsTroy Cobbley
I spoke to Dale again about changing the two warehouse doors to two 30".
FIRE-Conference6/26/20096/26/20096/29/2009PDONE
DetailsTroy Cobbley
Spoke to Dave about emergency ligt placement in warehouse
BLD-Conference6/23/20096/23/20096/23/2009PPASS
DetailsTroy Cobbley
I discussed new door hardware issues with the tenant.
BLD-Final6/8/20096/9/20096/9/2009AFAIL
DetailsMike Jordan
Marilyn Please call 15 min before going out Phone #: ###-#### x231. Provide sticker above door to read "These doors to remain unlocked while building is occupied." Remove thumbturn and manual flushbolts from main entry/exit and provide approved hardware. Remove thumb turn and manual flush bolts from second set of doors at main entry or remove doors. Provide lever type hardware on both exit doors from warehouse, and remove manual flush bolt and provide automatic flush bolt on front exit from warehouse. Provide exterior landing from rear exit of warehouse. c/n issued.
FIRE-Final Inspection6/8/20096/8/20096/9/2009PFAIL
DetailsTroy Cobbley
Provide single action hardware on both of the warehouse exit doors. Repair the exit sign and provide emergency lighting at the north warehouse exit door. Mount the fire extinguisher that is located in the front office. Apply for a racking storage permit.