BLD-Final | 6/25/2009 | 6/26/2009 | 6/26/2009 | P | PASS |
Jim Storey
|
|
|
Jimmy Phone #: ###-#### final ok card on site.
|
FIRE-Final Inspection | 6/25/2009 | 6/26/2009 | 6/26/2009 | A | PASS |
Forrest France
|
|
|
Correction notice items verified for completion, life safety passed.
|
BLD-Final | 6/24/2009 | 6/25/2009 | 6/25/2009 | P | FAIL |
Jim Storey
|
|
|
James Phone #: ###-#### Provide current annual certification for both fire extinguishers, lower mounting height at the west side extinguisher, remove the manual thumbturn at the main entry/exit and provide approved exit hardware, terminate exposed electrical wires in a junction box.
|
FIRE-Final Inspection | 6/24/2009 | 6/25/2009 | 6/25/2009 | A | FAIL |
Forrest France
|
|
|
Provide current annual certification for both fire extinguishers, lower mounting height at the west side extinguisher, remove the manual thumbturn at the main entry/exit and provide approved exit hardware, terminate exposed electrical wires in a junction box.
|