Permit Information
Permit NumberBLD09-01982
StatusFinaled
Name TYLER WESTOVER
Site Address 350 N MILWAUKEE ST Unit: 1051
Project NameBTS #1051
Customer Number 
ePlanReviewNo
Description
**(PARADIGM APPAREL INC. - Boise Town Square - STE#1051)** Application for inspection to determine requirements for issuance of a Certificate of Occupancy for an existing 2,417 square foot retail sales space. NO NEW WORK IS AUTHORIZED UNDER THIS PERMIT. There are no changes to occupancy or use under this permit. This building is fully fire sprinklerd any alterations to the sprinkler system shall be maintained per NFPA #13 as regulated by the fire department, The smoke evacuation system shall remain operational as originally installed under the 1985 UBC. Raking that exceeds 8 ft. in height requires a separate Building Permit be submitted and approved before installation. TLW
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final11/12/200911/13/200911/13/2009PPASS
DetailsMike Jordan
ryan Phone #: ###-####. ok for perm occ.
FIRE-Final Inspection11/12/200911/13/200911/13/2009APASS
DetailsTroy Cobbley
life safety passed
BLD-Final11/12/200911/12/200911/12/2009PNR
DetailsMike Jordan
RYAN Phone #: ###-####. Life/safety inspection failed.
FIRE-Final Inspection11/12/200911/12/200911/12/2009AFAIL
DetailsTroy Cobbley
The damper for the smoke evac system failed to operate when the smoke detector was activated. The other items have been corrected.
BLD-Final11/9/200911/10/200911/10/2009PNR
DetailsMike Jordan
Ryan Phone #: ###-#### PLEASE CALL 15 MIN BEFORE GOING OUT. life/safety failed.
FIRE-Final Inspection11/9/200911/10/200911/10/2009AFAIL
DetailsTroy Cobbley
See the city approved plans for a list of deficiencies which include providing testing/verification of the smoke evac system, provide emergency lighting in the main sales floor area, repair the existing emergency lighting in the rear exit corridor and mount the fire extinguisher and provide a current inspection tag.