FIRE-Final Inspection | 2/11/2010 | 2/12/2010 | 2/12/2010 | A | PASS |
Forrest France
|
|
|
Correction notice items field verified for completion, fire life safety inspection passed.
|
BLD-Final | 2/11/2010 | 2/12/2010 | 2/12/2010 | A | PASS |
Dave Hannah
|
|
|
Rob Phone #: ###-####
|
FIRE-Conference | 2/10/2010 | 2/10/2010 | 2/10/2010 | P | DONE |
Forrest France
|
|
|
Regarding previous correction items, fire sprinkler work and exceptions allowed per NFPA 13.
|
FIRE-Final Inspection | 2/9/2010 | 2/9/2010 | 2/9/2010 | P | FAIL |
Forrest France
|
|
|
Correction items include door hardware at four locations ( two main entry/exits-STE 301 and 302, office in 301, and backward panic in hallway at 302), provide missing escutcheons for fire sprinkler heads at various locations, post suite address at 302, need stamped plans and notes on site at next visit, two sprinkler heads are overspaced off the new partition wall.
|
BLD-Final | 2/9/2010 | 2/9/2010 | 2/9/2010 | P | CANC |
Dave Hannah
|
|
|
Rob Phone #: ###-####
|