FIRE-Final Inspection | 4/7/2010 | 4/7/2010 | 4/7/2010 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed.
|
BLD-Final | 4/6/2010 | 4/7/2010 | 4/7/2010 | A | PASS |
Tom Arcoraci
|
|
|
ellen Phone #: ###-####
|
FIRE-Final Inspection | 4/6/2010 | 4/7/2010 | 4/7/2010 | A | FAIL |
Troy Cobbley
|
|
|
All items have been corrected except the emergency lights do not switch to battery backup as required. The owner has been turning off the lighting circuit at the breaker panel thus depleting the batteries every night.
|
BLD-Final | 2/24/2010 | 2/25/2010 | 2/25/2010 | P | NR |
Tom Arcoraci
|
|
|
Ben please call before going out Phone #: ###-####
|
FIRE-Final Inspection | 2/24/2010 | 2/25/2010 | 2/25/2010 | A | FAIL |
Troy Cobbley
|
|
|
Provide approved hardware at the main exit door as discussed, repair the emergency light in the assembly room, provide emergency lighting in the Lounge and Hall areas, provide revised occupant load sign for 103 people and provide revised plans that show occupancy in the adjoining space that is listed as "Existing Office Space" on the city approved plans.
|