Permit Information
Permit NumberBLD10-00691
StatusFinaled
Name ANDERSEN CONSTRUCTION CO
Site Address 11311 W CHINDEN BLVD
Project NameHewlett Packard BLD 4
Customer Number 
ePlanReviewNo
Description
(HEWLETT PACKARD BLDG 4) Construct a 620 sq. ft. mechanical platform of steel beam, columns & grate on reinforced concrete slab with thickened footings at the NW exterior corner of the building for new HVAC equipment to service the new 560 sq. ft. UPS room and 240 sq. ft. communications room on the first floor and add new HVAC units to serve the existing communications rooms on the 2nd & 3rd floor. Special Inspection is required per Sheet S-00100. Perform select interior demolition of existing mech. and elect. service to UPS & communications rooms; construct 1-hour fire barrier around new UPS room with opening & penetrations protected; add new electrical equipment in existing electrical room and modify doors to swing out with panic hardware and upgrade sprinkler & alarm systems as necessary for code compliance at new work construction. Separate sprinkler and alrm permits are required before any modifications can be done, all as regulated by the fire department. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final6/21/20106/23/20106/23/2010APASS
DetailsJim Sly
Wes Phone #: ###-####
Certificate of compliance
DOC - Permit Finaled6/23/20106/23/20106/23/2010PPASS
DetailsJim Sly
FIRE-Final Inspection6/21/20106/22/20106/22/2010APASS
DetailsForrest France
Correction items per previous visit are finished, fire life safety final approved.
FIRE-Conference6/18/20106/18/20106/18/2010PDONE
DetailsForrest France
Regarding items remaining for fire life safety final and site inspection schedule.
FIRE-Conference6/14/20106/14/20106/14/2010PDONE
DetailsTroy Cobbley
Went over the signage requirements for the cabinet doors.
BLD-Final6/7/20106/8/20106/8/2010PNR
DetailsJim Sly
Wes Phone #: ###-####
FIRE-Final Inspection6/7/20106/8/20106/8/2010AFAIL
DetailsTroy Cobbley
Provide signage on the door into the UPS room and on the outside and inside of the electrical equipment/batterys as per the approved plans/notes. Also smoke detection is required in the UPS room as per the approved plans/notes.