BLD-Final | 6/21/2010 | 6/23/2010 | 6/23/2010 | A | PASS |
Jim Sly
|
|
|
Wes Phone #: ###-#### Certificate of compliance
|
DOC - Permit Finaled | 6/23/2010 | 6/23/2010 | 6/23/2010 | P | PASS |
Jim Sly
|
|
|
|
FIRE-Final Inspection | 6/21/2010 | 6/22/2010 | 6/22/2010 | A | PASS |
Forrest France
|
|
|
Correction items per previous visit are finished, fire life safety final approved.
|
FIRE-Conference | 6/18/2010 | 6/18/2010 | 6/18/2010 | P | DONE |
Forrest France
|
|
|
Regarding items remaining for fire life safety final and site inspection schedule.
|
FIRE-Conference | 6/14/2010 | 6/14/2010 | 6/14/2010 | P | DONE |
Troy Cobbley
|
|
|
Went over the signage requirements for the cabinet doors.
|
BLD-Final | 6/7/2010 | 6/8/2010 | 6/8/2010 | P | NR |
Jim Sly
|
|
|
Wes Phone #: ###-####
|
FIRE-Final Inspection | 6/7/2010 | 6/8/2010 | 6/8/2010 | A | FAIL |
Troy Cobbley
|
|
|
Provide signage on the door into the UPS room and on the outside and inside of the electrical equipment/batterys as per the approved plans/notes. Also smoke detection is required in the UPS room as per the approved plans/notes.
|