BLD-Aging Inspection | 7/25/2014 | 7/25/2014 | 7/25/2014 | | DONE |
Mike Jordan
|
|
|
|
DOC - Permit Expired | 7/25/2014 | 7/25/2014 | 7/25/2014 | P | PASS |
Mike Jordan
|
|
|
This tenant is no longer in this building. It is now occupied by probation and poarole, which has a C.O.
|
BLD-Aging Inspection | 12/17/2013 | 12/17/2013 | 12/18/2013 | | PEND |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 7/30/2013 | 7/30/2013 | 7/31/2013 | | CANC |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 3/13/2013 | 3/13/2013 | 3/20/2013 | | PEND |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 12/12/2012 | 12/12/2012 | 12/17/2012 | | PEND |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 9/11/2012 | 9/11/2012 | 9/14/2012 | | CANC |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 5/30/2012 | 5/30/2012 | 6/7/2012 | | CANC |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 2/3/2011 | 2/3/2011 | 2/4/2011 | | PEND |
Mike Jordan
|
|
|
Pending electrical inspection if needed.
|
FIRE-Final Inspection | 9/29/2010 | 9/30/2010 | 9/30/2010 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed.
|
FIRE-Final Inspection | 9/24/2010 | 9/24/2010 | 9/24/2010 | P | FAIL |
Troy Cobbley
|
|
|
The relocated exit sign does not function now and will need to be repaired and retested.
|
FIRE-Final Inspection | 9/14/2010 | 9/14/2010 | 9/14/2010 | P | FAIL |
Troy Cobbley
|
|
|
Occupancy is not allowed without a Certificate of Occupancy per IFC 105.3.3, provide emergency lighting and one fire extinguisher in the northeast end of the warehouse, repair the emergency light in the south end of the warehouse, provide exit discharge lighting at all four warehouse exit doors, provide single action hardware on both of the west facing warehouse doors, remove the exit sign fron the door leading into the warehouse through a locked door, relocate the exit sign in the north offices to the door leading into the south offices, add fire extinguisher in the south office area with tag as discussed. The annual inspection on all of the existing fire extinguishers are nearly expired.
|
BLD-Final | 9/13/2010 | 9/14/2010 | 9/14/2010 | A | FAIL |
Mike Jordan
|
|
|
Jim Phone #: ###-####. Needs life/safety final and CDHD final. Noted that building is occupied with no certificate of occupancy. Also noted that a plumbing, electrical and mechanical permits were required as per scope of work. This was discussed with Bob Hosak. Bob noted that these permits were not required and did not what the electrical inspector to make a determination if an electrical permit would be required. Will discuss with Bob Archibald.
|
FIRE-Conference | 8/31/2010 | 8/31/2010 | 8/31/2010 | P | DONE |
Troy Cobbley
|
|
|
I met Bob Hosack on site while performing a sprinkler inspection. While performing the sprinkler inspection I found that an AES fire alarm transmitter had been installed without permits. I notified Bob that I would hold up the occupancy of the new tenant until this new fire alarm work had been permited, issued and passed a final inspection. I also found that the fire sprinkler system had not been inspected in ten years and I let Bob know that would also need to be addressed. I noted that one sprinkler pendant in the office area was located too close to a wall and would need to be relocated.
|
BLD-Conference | 8/31/2010 | 8/31/2010 | 8/31/2010 | A | DONE |
Mike Jordan
|
|
|
|
BLD-Framing/Rough-in | 7/21/2010 | 7/22/2010 | 7/22/2010 | A | PART |
Mike Jordan
|
|
|
jim Phone #: ###-####. Interior steel stud framed walls at infill areas and from existing top of wall to roof dexk only, provided that all other trades permits are pulled and required inspections have been done. Noted no other trades permits have been issued at this time. Contacted Jack Frank (electrical inspector) and let him know about demo work done to this piont, and electrical permit may be required. Gave Jack the permit number, Doug Poedy to follow up as per Jack Frank. A correction notice was issued.
|
BLD-Framing/Rough-in | 7/20/2010 | 7/20/2010 | 7/20/2010 | P | FAIL |
Mike Jordan
|
|
|
Bob Phone #: ###-####. No approved plans on site. Correction Notice posted.
|