BLD-Final | 12/21/2010 | 12/21/2010 | 12/21/2010 | P | PASS |
Mike Jordan
|
|
|
Sid Mike they can now have there final I attached the electrical permit to the building pernit. any questions please call me Thanks Darla Phone #: ###-####. ok for perm occ.
|
BLD-Final | 12/7/2010 | 12/7/2010 | 12/7/2010 | P | PASS |
Mike Jordan
|
|
|
SID Phone #: ###-####. ok for perm occ.
|
FIRE-Final Inspection | 12/6/2010 | 12/6/2010 | 12/6/2010 | P | PASS |
Troy Cobbley
|
|
|
life safety passed
|
FIRE-Final Inspection | 11/29/2010 | 11/29/2010 | 11/29/2010 | P | FAIL |
Troy Cobbley
|
|
|
Sid and I found that the door mags are not connected to the fire alarm panel. Also Sid needs to get approval to use the alarm/intercom system for the common use restroom corridor.
|
FIRE-Final Inspection | 10/27/2010 | 10/28/2010 | 10/28/2010 | A | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for redlines on items that need corrected which include overspaced/missing sprinkler heads, inoperative exit signs/emergency lights, incorrect door hardware and I need verification that the access controlled egress doors are connected to the fire alarm system.
|
BLD-Conference | 10/27/2010 | 10/27/2010 | 10/27/2010 | P | DONE |
Mike Jordan
|
|
|
|
BLD-Conference | 10/26/2010 | 10/27/2010 | 10/27/2010 | A | CANC |
Mike Jordan
|
|
|
Sid Phone #: ###-####
|