Permit Number | BLD10-02119 |
Status | Finaled |
Name |
SUMMIT WALL SYSTEMS
|
Site Address |
11734 W EXECUTIVE DR
|
Project Name | |
Customer Number | |
ePlanReview | No |
Description |
(**VANILLA FINISH** - Building permit required before occupancy) Permit is to remodel an existing 8,570 square foot tenant space to become three different areas 11700 - 2,476 square feet (Summit Wall Systems) / 11734 - 4,821 square feet (Vanilla Finish - Building Permit Required before occupancy) / 11692 - 1,273 square feet (Dead Space - noncompliant tenant space). Approval contingent upon adhering to the approved plans on file. This space requires a permit before occupancy to address non-compliant issues: a mop sink is needed to comply with 2902.2 and barriers are required at the drinking fountain per sec 307 of ICC/Ansi. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. **TLW**
|