BLD-Final | 11/23/2010 | 11/24/2010 | 11/24/2010 | A | PASS |
Mike Jordan
|
|
|
Dean Phone #: ###-####. ok for perm occ.
|
FIRE-Final Inspection | 11/23/2010 | 11/24/2010 | 11/24/2010 | A | PASS |
Troy Cobbley
|
|
|
life safety passed.
|
BLD-Final | 11/23/2010 | 11/23/2010 | 11/23/2010 | P | NR |
Mike Jordan
|
|
|
Brad Phone #: ###-####
|
FIRE-Final Inspection | 11/23/2010 | 11/23/2010 | 11/23/2010 | P | FAIL |
Troy Cobbley
|
|
|
Provide an occupant load sign per review note #1, provide panic hardware per review note #5 and plan sheet #A-1, provide exit discharge lighting per drawing sheet E-1, and repair emergency lighting in the womens restroom.
|
BLD-Final | 11/22/2010 | 11/23/2010 | 11/23/2010 | A | NR |
Mike Jordan
|
|
|
Bill Phone #: ###-####
|
BLD-Framing/Rough-in | 11/16/2010 | 11/16/2010 | 11/16/2010 | P | PASS |
Mike Jordan
|
|
|
bill - ceiling insp Phone #: ###-####. Ceilin grid ok.
|
BLD-Framing/Rough-in | 10/25/2010 | 10/25/2010 | 10/25/2010 | P | PART |
Mike Jordan
|
|
|
bill - drywall Phone #: ###-####. 2nd. layer of 5/8 typex rock and fire caulking for penetrations, Needs to provide UL data.
|
BLD-Framing/Rough-in | 10/21/2010 | 10/22/2010 | 10/22/2010 | P | PART |
Mike Jordan
|
|
|
bill Phone #: ###-####. Screw pattern for 1st. layer of 5/8 type x rock at two firewall.
|
BLD-Framing/Rough-in | 10/20/2010 | 10/21/2010 | 10/21/2010 | P | PASS |
Mike Jordan
|
|
|
bill Phone #: ###-####. Interior steel stud framed walls and soffitt only.
|
BLD-Conference | 10/13/2010 | 10/14/2010 | 10/14/2010 | A | DONE |
Mike Jordan
|
|
|
bill Phone #: ###-####
|