Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberBLD10-02521
StatusFinaled
Name STEIN KEITH
Site Address 5656 W MORRIS HILL RD
Project NameStein Distributing
Customer Number 
ePlanReviewNo
Description
**(STEIN DISTRIBUTING)** Application for inspection to determine requirements for issuance of a Certificate of Occupancy for an existing 52,639 square foot storage building and offices. NO NEW WORK IS AUTHORIZED UNDER THIS PERMIT. This building was last permitted in 1989 under fiche #952091. There are no changes to occupancy or use under this permit. TLW
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection11/19/201011/22/201011/22/2010APASS
DetailsTroy Cobbley
Life safety passed. The Knox key box has been installed. All items pertaining to the high piled storage are to be addressed by the Boise City Fire Dept through a operational permit. This is per Scott Arellano and Mark Sentenno.
BLD-Final11/12/201011/16/201011/16/2010PPASS
DetailsTom Arcoraci
ryan Phone #: ###-#### or ###-#### ok for perm occ when fire signs off
FIRE-Final Inspection11/12/201011/16/201011/16/2010APART
DetailsTroy Cobbley
A temporary occupancy was given with Scotts permission until the Knox box that is on order has been installed.
BLD-Final11/2/201011/5/201011/5/2010APASS
DetailsTom Arcoraci
Ryan Phone #: ###-#### pending fire sign off
FIRE-Final Inspection11/2/201011/4/201011/4/2010PFAIL
DetailsTroy Cobbley
Provide emergency lighting for both the office and the warehouse areas. Provide additional exit door in warehouse. Provide verification on which doors are required to swing out. Remove all locking hatches and thumbturns. Provide automatic flush bolts on both main doors. Provide single action hardware on door from entrance office. Verify/provide at least a total of 13 (qty) "4A" classification fire extingguishers in the warehouse. Finish/final the project related fire alarm and fire sprinkler permits. Resubmit plans for review of high pile storage requirements of IFC chapter 23. Ryan Phone #: ###-####
FIRE-Final Inspection10/27/201010/29/201010/29/2010AFAIL
DetailsForrest France
Items discussed include fire sprinkler system work underway, door hardware, emergency lights, code review notes, trade permits, etc. Building is not in condition for final fire life safety approval at this time.
BLD-Final10/27/201010/29/201010/29/2010PCANC
DetailsTom Arcoraci
Ryan cell####-#### Phone #: ###-####//Tim Woodard wants you to also verify drain sink and related piping was removed from office/mezzanine area.//fire l/s failed so cancelled per Ryan Albers will call back to reschecule 10/29/10 11:02am//leg