FIRE-Final Inspection | 1/18/2011 | 1/18/2011 | 1/19/2011 | P | PASS |
Forrest France
|
|
|
Noted correction items field verified. Fire life safety passed.
|
BLD-Final | 1/18/2011 | 1/18/2011 | 1/18/2011 | P | PASS |
Dave Hannah
|
|
|
marcie Phone #: ###-####
|
FIRE-Final Inspection | 1/12/2011 | 1/12/2011 | 1/13/2011 | P | PART |
Forrest France
|
|
|
Final pending correction notice items.
|
FIRE-Conference | 12/23/2010 | 12/23/2010 | 12/23/2010 | P | DONE |
Forrest France
|
|
|
Regarding issued correction notice information.
|
BLD-Final | 12/6/2010 | 12/7/2010 | 12/7/2010 | A | NR |
Dave Hannah
|
|
|
before 11:30//Barbara Perry Bauer Phone #: ###-#### needs to finish fire life saftey corrections first
|
FIRE-Final Inspection | 12/6/2010 | 12/6/2010 | 12/6/2010 | P | FAIL |
Forrest France
|
|
|
See correction notice and permit documents on site for list of items including: post signage at the main entry/exit, provide approved door hardware at the main exit, post fire extinguisher as discussed, repair exposed electrical wiring at the storage closet light fixture.
|