BLD-Final | 10/24/2011 | 10/25/2011 | 10/25/2011 | P | PASS |
Mike Jordan
|
|
|
Mark Phone #: ###-####. Ok for perm. occ.
|
FIRE-Final Inspection | 10/24/2011 | 10/25/2011 | 10/25/2011 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed. During the inspection I found that a Class II combustible liquid is going to be stored in the building along with the originally submitted and approved Class III. The maximum amount of the Class II will be 240 gallons. The Class III is still limited to 1,000 gallons. If the limits are to be exceeded the building will need to be reviewed for an H occupancy. The shop manager was notified of this and the revised fire dept review comments have been left on site with the original approved plans.
|
BLD-Final | 10/20/2011 | 10/21/2011 | 10/21/2011 | A | NR |
Tony Young
|
|
|
mark Phone #: ###-####,, needs underground sprinkler and fire/lifesaftey final,,, called and left a message
|
BLD-Other | 8/4/2011 | 8/4/2011 | 8/4/2011 | P | DONE |
Troy Cobbley
|
|
|
A stop work order is being issued by Troy Cobbley due to sheet rock being installed without approval and prior to portions of the sprinkler system being installed. Notices were posted on site. The building contractor was not on site to discuss the situation.
|
BLD-Energy code compliance | 7/25/2011 | 7/26/2011 | 7/26/2011 | A | PASS |
Mike Jordan
|
|
|
MARK Phone #: ###-####
|
BLD-Framing/Rough-in | 7/19/2011 | 7/20/2011 | 7/20/2011 | A | PASS |
Mike Jordan
|
|
|
Mark Phone #: ###-####
|
BLD-Framing/Rough-in | 7/18/2011 | 7/19/2011 | 7/19/2011 | A | FAIL |
Mike Jordan
|
|
|
Mark Young Phone #: ###-####. Provide special inspectio reports for concrete and masonry, Strap top plates in breakroom, shear wall inspection? Complete airseal pack and fireblock top plates at all penetrations. correction notice issued.
|
BLD-Foundation | 6/7/2011 | 6/7/2011 | 6/7/2011 | P | PASS |
Mike Jordan
|
|
|
Brent Phone #: ###-####
|
BLD-Footing | 6/2/2011 | 6/3/2011 | 6/3/2011 | A | PART |
Mike Jordan
|
|
|
BRENT Phone #: ###-####. WSork min progress. Aslo needs special inspection.
|